Safety Integrated
4.1 SINAMICS Safety Integrated
Grouping drives
If the function is to be simultaneously initiated for several drives, the terminals for the
corresponding drives must be grouped together:
● Control Unit
● Motor Module
Example: Terminal grouping for safe standstill (SH)
The "Safe standstill" function should be able to be selected/deselected separately for group
1 (drive 1 and 2) and group 2 (drive 3 and 4).
The same grouping for the safe standstill must be performed for both the Control Unit and for
the Motor Modules.
4-4
By appropriately interconnecting the binector input to a joint input terminal for the drives
to be combined to form a group.
By appropriately connecting terminal "EP" for the individual Motor Modules belonging to a
group.
Note
The same grouping must be set in both monitoring channels.
If a fault in a drive causes the safe standstill (SH), the other drives of the same group will
not automatically be placed in the safe standstill (SH).
Guide for the SINUMERIK 840D sl machine configuring
Manual, 07/2006 Edition, 6FC5397-6CP10-0BA0