Allen-Bradley A Series Installation Instructions Manual page 13

Devicenet network powered 16-input module
Hide thumbs Also See for A Series:
Table of Contents

Advertisement

DeviceNet ArmorBlock™ Network Powered 16-input Module
(1)
Input Off-to-On or On-to-Off delay is time from a valid input signal to recognition by the module.
(2)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
(3)
Refer to Connection Systems, publication C116-CA508.
Environmental Specifications
Attribute
Temperature, operating
Temperature, surrounding air, max. 60 °C (140 °F)
Temperature, nonoperating
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
ESD immunity
Radiated RF immunity
EFT/B immunity
Value
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60 °C (-4...140 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
IEC 61000-4-2:
8 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4:
±3 kV @ 5 kHz on signal ports
±2 kV @ 5 kHz on communication ports
Publication 1732D-IN007B-EN-E - November 2011