ArmorPoint 24V dc Output Modules, Series A Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices.
Page 3
Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
ArmorPoint 24V dc Output Modules, Series A Preventing Electrostatic Discharge ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static.
Page 5
4. Ground the system using the ground lug connection. (The ground lug connection is also a mounting hole.) Mounting base Keyswitch- Set to position 1 for the 1738 digital output modules Ground lug connection 43675 Latching mechanism Allen-Bradley Replacements Publication 1738-IN001A-EN-E - June 2004...
ArmorPoint 24V dc Output Modules, Series A Install the ArmorPoint To install the ArmorPoint digital output module, proceed as follows. Digital Output Module 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 1 aligns with the notch in the base.
Output 6 (M12-D) Pin 3 - Common Pin 5 - No Connect 43664 Make sure all connectors and caps are securely ATTENTION tightened to properly seal the connections against leaks and maintain IP67 requirements. Allen-Bradley Replacements Publication 1738-IN001A-EN-E - June 2004...
ArmorPoint 24V dc Output Modules, Series A Communicate With I/O messages are sent to (consumed) and received from (produced) the ArmorPoint I/O modules. These messages are mapped into the Your Module processor’s memory. These ArmorPoint I/O output modules produce 1 byte of input data (scanner Rx - status). They consume 1 byte of I/O data (scanner Tx).
Flashing Red/Green Communication faulted device - the device has detected a network access error and is in communication faulted state. Device has received and accepted an Identity Communication Faulted Request - long protocol message. Allen-Bradley Replacements Publication 1738-IN001A-EN-E - June 2004...
ArmorPoint 24V dc Output Modules, Series A Indication Probable Cause I/O Status Output is inactive Yellow Output is active and under control Flashing Red Open circuit detection. No load. (Off-State only) Short circuit detected. (On-State only) Specifications Following are specifications for the 1738 ArmorPoint digital output modules.
Page 11
Meets IP65/66/67 (when marked) Mounting Base Screw Torque #8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel 1 - on signal ports Wiring Category Weigh Imperial (Metric) 0.637 lb. (0.289 kg) Allen-Bradley Replacements Publication 1738-IN001A-EN-E - June 2004...
Page 12
ArmorPoint 24V dc Output Modules, Series A General Specifications (continued) Certifications: c-UL-us UL Listed Industrial Control Equipment, (when product is marked) certified for US and Canada European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326;...
Page 13
ArmorPoint 24V dc Output Modules, Series A Notes: Allen-Bradley Replacements Publication 1738-IN001A-EN-E - June 2004...
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.