Step-By-Step Installation Instructions; Required Tools - Tesla Powerwall Installation Manual

Hide thumbs Also See for Powerwall:
Table of Contents

Advertisement

Warning: Powerwall must be installed by a Tesla Energy Certified Installer.
STEP 1 - REMOVE THE LID AND BOTTOM COVER
STEP 2 - REMOVE THE SPLASH COVER
STEP 3 - SET THE COMMUNICATION SWITCHES
STEP 4 - SET THE ADDRESS SWITCHES
STEP 5 - PREPARE THE WIRING
STEP 6 - CONNECT THE WIRING
STEP 7 - ATTACH THE SPLASH COVER
STEP 8 - REMOVE THE PALLET
STEP 9 - DETERMINE THE MOUNTING LOCATION FOR POWERWALL
STEP 10 - INSTALL THE WALL MOUNT BRACKET
STEP 11 - MOUNT POWERWALL
STEP 12 - REMOVE THE PACKAGING
STEP 13 - FEED WIRES THROUGH THE CONDUIT PLATE OR CABLE GLAND
STEP 14 - CONNECT MULTIPLE POWERWALLS TOGETHER
STEP 15 - CONNECT POWERWALL TO THE INVERTER
STEP 16 - ATTACH THE SIDE COVERS
STEP 17 - ATTACH THE BOTTOM COVER
STEP 18 - REPACK THE SHIPPING BOX

REQUIRED TOOLS

Wall mount bracket fasteners
Note: The details below are only guidance and are not guaranteed to be applicable. Consult
local building codes and a structural engineer to ensure the use of appropriate fasteners.
Minimum of 6 fasteners, stainless steel, diameter 10 mm (3/8 in)
Fastener head clearance for all positions but two bottom outer holes: 18 mm (11/16 in)
Fastener head clearance for bottom two holes at 600 mm (24 in) spacing: 8 mm (5/16 in)
Washers between fastener heads and wall mount bracket are recommended
Drill and a drill bit suitable for drilling pilot holes in the desired mounting surface
Socket wrench
10 mm socket adapter (for covers and wall mount bracket side tabs)
17 mm socket adapter (for wood block bolts)
Large flathead screwdriver (for ground lug)
Optional: small flathead screwdriver (for wiring terminal tabs)
T20 Torx (for splash cover and screws fastening box to wood blocks)
T30 Torx (for packaging L-bracket and conduit/gland plate)
Torque wrench
Stud finder (for wood installations)
Level tool
Painter's tape and/or pencil
Wire stripper and wiring (as described in
Conduit fitting or cable gland (as appropriate)
Lift tool or adequate personnel trained and capable of lifting 115 kg (254 lb) from ground level
to approximately chest height
Warning: Powerwall is heavy and challenging to lift. Lift equipment is recommended.
To prevent injury, wear work boots (preferably steel-toed), long pants, and gloves.
Tesla Energy

Step-by-Step Installation Instructions