Page 1
Manual No: 577013-719 Revision: G TLS-IB Site Prep Manual...
Page 2
Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication.
......................12 Mounting the TLS-IB ....................14 Cable Specifications .....................15 Field Wiring ........................16 Probe to TLS-IB Location (Level 1 Installations Only) ........16 Maximum Cable Lengths ..................16 Ducting Entry to TLS-IB Location ................16 Equipment Connected To The RS-232 Port ..............16 Site Prep - U.S and Canadian Installations National Electrical Code Compliance ................17...
Page 4
.................40 Signal Input Specifications ...................41 TLS-IB IFSF Commands ....................41 Figures Figure 1. Control Drawing Showing an Example TLS-IB System Site Layout...3 Figure 2. Typical Tank Lid Access Chamber Installation ........7 Figure 3. Tank Lid Access Chamber — Critical Dimensions .........7 Figure 4.
Page 5
Cord Grip and Cap Kit (Part No. 330020-282) ........Table 6. Metal Cap and Ring Kit (Part No. 312020-952)........Table 7. TLS-IB Serial Communication / IFSF Node Address Selections..Table 8. TLS-IB Serial Interface Connections ............ Table 9. TLS-IB Serial Commands..............
Introduction T h i s m a n u a l d e s c r i b e s s i t e p r e p a r a t i o n a n d i n s t a l l a t i o n p r o c e d u r e s f o r t h e T L S - I B a n d M a g P r o b e s . S i t e p r e p a r a t i o n i s d i v i d e d i n t o I n t e r n a t i o n a l a n d U .
Page 7
Read and understand all manuals thoroughly. If you do not understand a procedure, ask someone who does. WARNING STATIC SENSITIVE COMPONENTS Heed the adjacent instructions to Wear grounded anti-static wrist strap avoid equipment damage or personal before handling a TLS-IB CPU board. injury.
Circuitry within the TLS-IB Console barrier forms an intrinsically safe, energy-limited system. This system makes TLS-IB probes safe for use in a Class I, Group D hazardous location. TLS-IB probe wiring is intrinsically safe only when connected to Veeder-Root's TLS-IB Consoles.
Site Prep - International Installations General T h i s d o c u m e n t d e s c r i b e s t h e p r o c e d u r e s n e c e s s a r y t o p r e p a r e t h e s i t e , r e a d y f o r t h e i n s t a l l a t i o n o f t h e V e e d e r – R o o t T L S S e r i e s U n d e r g r o u n d S t o r a g e T a n k M o n i t o r i n g S y s t e m s .
TLS-IB Site Prep Manual Health and Safety I M P O R T A N T ! U n l e s s s t a t e d o t h e r w i s e , i n s t r u c t i o n s i n t h i s m a n u a l r e f e r t o b o t h l e v e l s o f s i t e p r e p a r a t i o n IN–TANK PROBES...
TLS-IB Site Prep Manual Tank Lid Access Chambers DANGER AREAS WARNING TLS System products will be operated near the highly combustible environment of a fuel storage tank. Failure to install these products according to the instructions contained in this manual may result in explosion and personal injury.
TLS-IB Site Prep Manual Tank Lid Access Chambers Veeder-Root Foam Plug Riser Assembly Dedicating Ducting Mag Probe Probe Cable to TLS-IB uk\tls\tnklidnt.eps Figure 2. Typical Tank Lid Access Chamber Installation I M P O R T A N T ! T o a l l o w a d e q u a t e s p a c e f o r p r o b e i n s t a l l a t i o n a n d s e r v i c i n g , i t i s r e c o m m e n d e d t h a t t h e a c c e s s c h a m b e r i s a m i n i m u m 7 5 0 m m d e e p a n d 6 0 0 m m w i d e a t t h e b a s e ( s e e F i g u r e 3 o n p a g e 7 ) .
TLS-IB Site Prep Manual European Probe and Riser Installation Criteria (Non-PTB) W h e r e m e c h a n i c a l o v e r f i l l p r e v e n t i o n d e v i c e s a r e i n s t a l l e d , c o n t r a c t o r s m u s t e n s u r e t h a t n o p a r t o f t h e s e d e v i c e s w i l l b e o b s t r u c t e d w h e n t h e p r o b e a n d r i s e r a s s e m b l y i s i n s t a l l e d .
TLS-IB Site Prep Manual European Probe and Riser Installation Criteria (Non-PTB) • W h e r e v e r p o s s i b l e , t h e p r o b e c a n i s t e r s h o u l d b e c o m p l e t e l y c o n t a i n e d w i t h i n t h e 3 - i n c h r i s e r . I f t h i s i s n o t p o s s i b l e , a p r o b e s l e e v e k i t m u s t b e u s e d .
Figure 9. The Veeder-Root Riser Cap Assembly and Fitting Tool I M P O R T A N T ! V e e d e r – R o o t s t r o n g l y r e c o m m e n d t h e u s e o f t h i s r i s e r a s s e m b l y .
TLS-IB Site Prep Manual PTB Compliant Installation R e m o v e t h e p l u g f r o m t h e t a n k s o c k e t . I n s t a l l a 3 - i n c h ( 8 0 m m n o m i n a l b o r e ) r i s e r u s i n g a n a p p r o p r i a t e t h r e a d s e a l i n g c o m p o u n d .
TLS-IB Site Prep Manual TLS-IB Location DETERMINING THE MINIMUM ACCESS CHAMBER DEPTH T h e m i n i m u m a c c e s s c h a m b e r d e p t h , i s c a l c u l a t e d a s f o l l o w s : 1 .
(for 240 Vac), or a Conduit for probe dedicated circuit breaker field cables rated for 15 amperes, 120 Vac or 240 Vac. NOTE, circuit breaker must be marked as the power disconnect for the TLS-IB Console. tlsnt\tlsibmnt.eps Figure 11. Typical TLS-IB Installation...
TLS-IB Site Prep Manual Cable Specifications Cable Specifications T h e c a b l e t y p e t a b l e s l i s t e d b e l o w f o r m p a r t o f t h e i n d i v i d u a l s y s t e m A T E X a p p r o v a l . S u b s t i t u t i o n o f c a b l e m a y i m p a i r i n t r i n s i c s a f e t y a n d m a y i n v a l i d a t e s y s t e m a p p r o v a l .
A m a x i m u m o f 3 0 5 m e t r e s o f c a b l e l e n g t h p e r s e n s o r o r p r o b e m u s t b e o b s e r v e d . DUCTING ENTRY TO TLS-IB LOCATION C o n n e c t i o n t o t h e T L S - I B m a y o n l y b e m a d e b y a V e e d e r –...
Site Prep - U.S and Canadian Installations National Electrical Code Compliance T h e f o l l o w i n g i n f o r m a t i o n i s f o r g e n e r a l r e f e r e n c e a n d i s n o t i n t e n d e d t o r e p l a c e r e c o m m e n d e d N a t i o n a l E l e c t r i c C o d e ( N E C ) p r o c e d u r e s .
Improper installation may result in fire or explosion causing serious injury or death. 1. Read thoroughly and follow the instructions shipped with each probe. 2. Probe wiring must enter the TLS-IB only through their designated areas. 3. Power wires and conduit must not enter the intrinsically safe compartment of the TLS-IB.
TLS-IB Site Prep Manual Determining Length of Probe When Used in a Dedicated Riser 3 . S u b t r a c t ( B ) f r o m ( A ) t o d e t e r m i n e t h e c o r r e c t t a n k d i a m e t e r ( C ) . R o u n d t a n k d i a m e t e r ( C ) u p t o n e x t h i g h e s t i n c h a n d o r d e r t h i s l e n g t h p r o b e .
TLS-IB Site Prep Manual Optional Kits for Series Mag Probe Installations Optional Kits for Series Mag Probe Installations KIT REQUIRED FOR AN AST INSTALLATION A n a d d i t i o n a l k i t i s n e e d e d t o i n s t a l l M a g p r o b e s i n t o a n a b o v e g r o u n d s t o r a g e t a n k ( A S T ) . T h i s k i t c o n t a i n s a l e n g t h o f f l e x i b l e c o n d u i t , c o n n e c t o r s , e t c .
TLS-IB Site Prep Manual Riser Cap Kit for Mag Probe Installations Riser Cap Kit for Mag Probe Installations T h e r i s e r i n w h i c h t h e M a g P r o b e i s i n s t a l l e d m u s t b e m o d i f i e d t o a l l o w t h e M a g P r o b e ’ s c a b l e t o e x i t t h e r i s e r . T h i s c a p d o e s n o t s u p p o r t t h e M a g P r o b e i t s e l f , w h i c h r e s t s o n t h e t a n k b o t t o m , b u t i t d o e s s e a l t h e r i s e r p i p e w h i l e a l l o w i n g t h e M a g P r o b e c a b l e t o p a s s t h r o u g h .
TLS-IB Site Prep Manual Riser Cap Kit for Mag Probe Installations Table 6. Metal Cap and Ring Kit (Part No. 312020-952) Quantity Description Part Number Group Cord Grip 331028-001 probes\cap&ring.eps Note: watch orientation Metal cap of bevels and tapers w/1/2" NPT...
TLS-IB Site Prep Manual Mag Probe Installation Mag Probe Installation NOTE R e f e r e n c e m a n u a l n u m b e r 5 7 7 0 1 3 - 5 7 8 f o r a d d i t i o n a l i n s t a l l a t i o n i n s t r u c t i o n s s p e c i f i c t o A T E X r e q u i r e m e n t s .
Page 29
TLS-IB Site Prep Manual Mag Probe Installation Use bushing and body of grip Flexible metal conduit fitting supplied with probe and supplied with AST kit Adaptor nut supplied with Liquidtight AST kit. fittings from AST kit Weatherproof junction box with 1/2"...
1. Read thoroughly and follow the instructions shipped with each probe. 2. Probe wiring conduit must not contain any other wires. 3. Probe wiring and conduits must enter the TLS-IB only through their designated areas (see Figure 12). 4. Power and communication wires and conduit must not enter the intrinsically safe compartment of the TLS-IB.
Epoxy sealed connections in a weatherproof junction box. Figure 23. Field Wiring probes to TLS-IB Cables Sealing Field Connections WIRING RUN THROUGH RIGID CONDUIT 1 . P u l l t h e w i r e s f r o m t h e p r o b e c a n i s t e r i n t o t h e j u n c t i o n b o x . P u l l t w o w i r e s f r o m t h e T L S - I B t h r o u g h t h e s e a l - o f f b o x a n d i n t o t h e j u n c t i o n b o x .
TLS-IB Site Prep Manual Mounting the TLS-IB From probe, sensor, or transducer To console Make sure that the ends of cable sheathing are sub- merged in sealant Tie wrap Wire nuts Instructions: NOTE: When temperature is below 50˚F (10˚C), keep 4.
2. Refer servicing to trained and qualified personnel only. 3. Substitution of components may impair intrinsic safety. 4. Be sure AC power is “Off” before opening the TLS-IB cover and connecting probe wires. Do not short any voltage across any barrier terminal including probes.
2. Refer servicing to trained and qualified personnel only. 3. Substitution of components may impair intrinsic safety. 4. Be sure AC power is “Off” before opening the TLS-IB cover and connecting wiring. 1 . W i t h A C p o w e r s w i t c h e d O f f , c o n n e c t t h e I F S F n e t w o r k w i r e s t o J 8 i n t h e T L S - I B a s s h o w n i n F i g u r e 2 6 b e l o w :...
I F S F n o d e a d d r e s s o f 0 6 , s e t s w i t c h e s 2 a n d 4 u p , a n d s w i t c h e s 1 a n d 3 d o w n . Table 7. TLS-IB Serial Communication / IFSF Node Address Selections...
Figure 27. Connecting serial communication wiring to TLS-IB Connecting Power Wiring to TLS-IB WARNING The TLS-IB contains voltages which can be lethal. It is connected to devices that must be intrinsically safe. Connecting power wires to a live circuit can cause electrical shock that may result in serious injury or death.
Page 38
R12-001 SGL DBL Protective Earthing R12-002 R12-003 R12-004 Conductor (Green and R12-005 R12-006 Yellow) Attach #12AWG (4 mm ) barrier ground IFSF wire to ground lug Power Intrinsically Side Safe Side esso\ibpowr.eps Figure 28. Wiring AC Power to the TLS-IB...
TLS-IB Site Prep Manual PROM Chip Replacement (Software Upgrade) PROM Chip Replacement (Software Upgrade) T h e P R O M c h i p ( U 2 9 ) i s r e p l a c e d w h e n a s o f t w a r e u p g r a d e i s i n s t a l l e d . T h i s p r o c e d u r e r e q u i r e s t h a t y o u p e r f o r m a R A M c l e a r .
Page 41
TLS-IB Site Prep Manual PROM Chip Replacement (Software Upgrade) Chip socket Chip Removal Tool (Digikey Part No. K293-ND, Removable or equivalent) chip Lifting hooks Chip removal slots Chip socket Chip Removal Tool (P/N 576036-022) lifting hooks Incorrect Correct go down in...
TLS-IB Site Prep Manual Replacing the Power Supply Board STATIC SENSITIVE - WEAR GROUNDED ANTI-STATIC WRIST STRAP BEFORE HANDLING THIS BOARD! PROM chip (U29) NODE 1) Orient PROM so that the small indented dot on ADDRESS top of the chip is on the same side with the small TLS-IB CPU BOARD triangle embossed in the socket's base;...
TLS-IB Site Prep Manual Neuron Service Switch 4 . T h e P o w e r S u p p l y b o a r d i s s e c u r e d b y t w o T - 1 5 T o r x s c r e w s i n t h e t o p o f t h e b o a r d . A f t e r r e m o v i n g t h e T o r x s c r e w s , s l o w l y l i f t u p o n t h e b o a r d u n t i l t h e l o w e r t a b s o n t h e b o a r d c l e a r t h e s l o t s i n t h e b o t t o m o f t h e T L S - I B , t h e n c o n t i n u e t o l i f t t h e b o a r d o u t .
TLS-IB Specifications Physical Specifications • W i d t h w / d o o r c l o s e d : 1 8 8 m m ( 7 . 6 ” ) - W i d t h w / d o o r o p e n : 2 3 5 m m ( 9 . 6 ” ) .
J 7 ( o n T L S - I B P o w e r S u p p l y B o a r d , s e e F i g u r e 2 7 o n p a g e 3 2 ) a r e s h o w n i n T a b l e 8 . Table 8. TLS-IB Serial Interface Connections...
TLS-IB Site Prep Manual Signal Input Specifications Table 9. TLS-IB Serial Commands Command Description Probe Fast Average Buffers Probe Standard Average Buffers Signal Input Specifications • U p t o 8 V e e d e r - R o o t M a g n e t o s t r i c t i v e p r o b e s c a n b e m o n i t o r e d .
TLS-IB Site Prep Manual TLS-IB IFSF Commands Table 11. Tank Level Gauge Error Code Database Data Identification Data Element Name TLG_Error_Type_Mes Table 12. Tank Probe Database Data Identification Data Element Name TP_Manufacturer_Id TP_Type TP_Serial_Nb TP_Model TP_Appl_Software_Ver TP_Status TP_Alarm Product_Level Water_Level TP_Status_Message Table 13.
Page 48
For technical support, sales or other assistance, please visit: www.veeder.com...
Need help?
Do you have a question about the TLS-IB and is the answer not in the manual?
Questions and answers