JUMO safetyM TB/TW Operating Instructions Manual page 49

Temperature limiter, temperature monitor
Table of Contents

Advertisement

Description
Relay contact between
terminals 9, 10 or 9, 12
does not switch.
Double LED lit (green and
red simultaneously)
2011-12-31
Cause
-
The fitted safety fuse in the pole arm 9 is
faulty.
-
Internal system error
Remedy
h
Measure terminals 9 and 10 of the relay with
a continuity tester when LED K1 shows
green.
h
Measure terminals 9 and 12 of the relay with
a continuity tester when LED K1 is off
h
The instrument must be returned to JUMO
for repair.
v
Chapter 2.1 "Service addresses"
- Switch the supply off and then back on again
If this does not help, the instrument must be
returned to JUMO for repair.
v
Chapter 2.1 "Service addresses"
13 What if...
47