C111 Analog Inputs - JUMO safetyM TB/TW Operating Instructions Manual

Temperature limiter, temperature monitor
Table of Contents

Advertisement

2011-12-31
7.1

C111 Analog inputs

Analog input
001
Pt 100
EN 60751
006
Pt 1000
EN 60751
601
KTY11-6 PTC
003
Pt 100
EN 60751
005
Pt 1000
EN 60751
024
2x Pt 100 DIN
k
Factory setting
Comment
in 3-wire circuit
in 3-wire circuit
sensor in 2-wire circuit
in 2-wire circuit
in 2-wire circuit
for differential measurement
The TB/TW can measure the differential of two Pt 100 resistance thermometers in a 2-wire
circuit.
Measurement input INP (terminal 1 and 2) acquires the first temperature.
The second measurement input IN2 (terminal 2 and 3) acquires the second temperature.
The differential DIF = INP - IN2 is displayed and evaluated.
Setting range for ALD: -1999 to 9999
7 Configuration level
Setting range for AL:
(can be restricted via
setup)
-1999 to +9999°C
-1999 to +9999°C
-1999 to +9999°C
-1999 to +9999°C
-1999 to +9999°C
-1999 to +9999°C
20
Limits for
overrange/
underrange
-205°C/ +855°C
-205°C/ +855°C
-55°C/ +155°C
-205°C/ +855°C
-205°C/ +855°C
-205°C/ +855°C