2011-12-31
7.10 SCL, SCH, AL LO, AL HI, OFFS, HYST1, HYST2
Function
SCL
lower limit of standard signal
SCH
upper limit of standard signal
AL LO
lower limit of the setting range for
limit value AL and warning alarm VA
AL HI
upper limit of the setting range for
limit value AL and warning alarm VA
OFFS
Measurement offset
HYS1
Limit value switching differential
HYS2
Warning alarm switching differential
7.11 C 120 Limit value for relay switching operations
Meaning
Limit-value for relay switching operations
This is where the total number of permissible relay switching operations is set.
If the limit-value for relay switching operations (C121) is higher than this Limit-
value, error message 0001 is displayed immediately and the relay is de-
energized.
If "0" is set, the function is inactive.
7 Configuration level
Comment
only when C111 set with 52, 53, 63, 71
only when C111 set with 52, 53, 63, 71
Must fall within the measuring range of the
connected sensor or standard signal!
maximum adjustment: -1999 to 9999
With measurement offset, a measured value
can be corrected by a programmable value.
0 to 100
0 to 100 (only when C119 = 1 or C119 = 2)
28
Value range
(factory
setting in bold)
-1999 to 0 to 9999
-1999 to 100 to 9999
-1999 to 9999
-1999 to 9999
-1999 to 0 to 9999
0 to 1 to 100
0 to 1 to 100
Value range
(factory setting in bold)
0 to 1000 to 9999