7.2

C112 Setting for a double thermocouple

Double thermocouple
0
no
1
yes
7.3

C113 Unit, decimal place

Unit, decimal place
0
°C, no decimal place
1
°C, one decimal place
2
°F, no decimal place
3
°F, one decimal place
7.4

C114 Device function

Device function
0
Initial commissioning of TB
temperature limiter
1
Temperature limiter TB
2
Temperature monitor TW
2011-12-31
Comment
sensor short circuit not detected!
only available for C111 from 037 to 048
v
Chapter 7.1 "C111 Analog inputs"
Can detect a sensor short circuit
Comment
A
When the unit changes to °F, the measurement is
converted. All other measurement-related values,
such as AL, are unchanged!
Comment
Whatever the switching state of the relay before the power failure, the TB
remains locked when the power returns.
Release is only necessary if the temperature is exceeded
Automatic release