Error Messages - JUMO safetyM TB/TW Operating Instructions Manual

Temperature limiter, temperature monitor
Table of Contents

Advertisement

2011-12-31
12

Error messages

Error display (code)
0002
0003
0004
0005
0006
0007
Cause
The total number of relay switching
operations has been reached.
Terminal temperature
is outside the -10 to 80°C range
Reference voltage
The measured value is above 999 or below
-999 and is thus outside the 3-digit display
range.
Calibration constant
Configuration data
Value cannot be displayed (too large or too
small)
reserved
reserved
12 Error messages
Remedy
h
Increase the total number of relay switching
operations
v
Chapter 7.11 "C 120 Limit value for relay
switching operations"
h
Acknowledge with the Reset key
v
Chapter 7.12 "C 121 Count for relay switching
operations"
h
Check the ambient temperature
h
Acknowledge with the Reset key
If that does not help, send the instrument in
-
A/D converter error
h
Acknowledge with the Reset key
If that does not help, send the instrument in
The instrument must be returned to JUMO for repair.
h
Send the instrument in
v
Chapter 2.1 "Service addresses"
-
-
44