Troubleshooting - Emerson XJ200 Installation And Operating Instructions Manual

Table of Contents

Advertisement

technical bulletin

Troubleshooting

Problem
Device does not appear on
supervisory controller.
Device appears on
supervisory controller, the
status goes "off
returns to "on
line"
few
minutes.
Device appears on
supervisory controller but
status is "off line".
All devices appear on
supervisory controller but
status is "off line".
A slave module is removed
from the network but
other modules seem to go
"off line" with it.
A new slave module is
added to the network but
it does not appear as "on
line" on the supervisory
controller.
Document Part # 026-4833 Rev 0 26-FEB-2013
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
XJ200 Installation and Operating Instructions
Possible Cause
Device not commissioned in
supervisory controller.
Communication may have
been delayed to the
line"
but
supervisory controller.
after a
Master is not reporting slave
module to the supervisory
controller.
Master is not communicating
with Slave modules.
When a module is removed
from the network, the master
reconfigures the best
communication path to all
remaining slave modules.
Ensure the line of sight to the
master is not obstructed.
Table 2 - Troubleshooting Guide for XJ200 Devices
Possible Solution
Follow commissioning procedures for
supervisor controller.
Check the supervisory
controller's
communication summary for percentage of
lost
packets.
If problem remains constant
with one particular module, reposition that
module or add a repeater.
Slave module is not communicating with the
master. Press Test button on slave module
and allow ample time to establish
communication. If the yellow LED remains
on, reposition the slave module to improve
line of sight with the master.
Ensure that you have followed the
installation steps in the proper order. A good
communication path needs to be
established between the master and slaves
before connecting the supervisory controller
and commissioning devices. Install the
master as high as possible to ensure optimal
coverage.
Allow ample time for the master to
reconfigure the communication path. If
other modules do not return "on line" press
the Test button on the slave module that is
"off line". If the module does not return "on
line", it is possible that communication is
blocked. If this is the case, reposition the
slave module or add a repeater between the
master and slave.
Press the Test button and allow ample time
for the master to establish a new
communication path.