Connect the module's MODBUS wires to the E2 MODBUS network. The MODBUS wires have
reversed polarities. The device can't be used with the E2 right away. You may need to config-
ure the device first and connect it to the E2.
NOTE: The wiring polarity between the XJ200 and E2 is reversed.
E2 Property Location
Menu-7-3-1-C7
Menu-7-3-1-C7
Menu-7-3-1-C7
Document Part # 026-4833 Rev 0 26-FEB-2013
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
XJ200 Installation and Operating Instructions
Figure 15 - Dixell MODBUS Networking
E2 Property
MODBUSOffLnDly
MOD1 Rsp Delay
MOD1 Msg Delay
Table 1 - E2 MODBUS Delay Settings
New Value
00:02:00
800 ms
30 ms
Page 12 of 17