E2S BExBG21D Instruction Manual

Flameproof xenon beacon for use in flammable gas and dust atmospheres

Advertisement

Quick Links

1) Introduction
The BExBG21D is a flameproof beacon certified to meet the
requirements of the ATEX directive 94/9/EC and the IECEx
scheme. The beacon produces synchronised visual warning
signals and can be used in hazardous areas where
potentially flammable gas and dust atmospheres may be
present. The BExBG21D has can be used in Zone 1 and
Zone 2 areas with gases in groups IIA, IIB and IIC and
Temperature Classifications of T1, T2, T3 and T4 in an
ambient temperature up to +55ºC. The beacon can also be
used at an ambient temperature up to +70ºC with a
temperature classification of T3. The units can be used in
Zone 21 and Zone 22 areas for combustible dusts and have
an IP rating of IP 67 and a surface temperature rating of
T135ºC if the upper ambient temperature is restricted to
+55ºC or T200ºC with an the upper ambient temperature of
+70ºC. The BExBG21D beacon has two xenon tubes and
can produce three different flash patterns.
2) Marking
All units have a rating label, which carries the following
important information:-
BExBG21D
Unit Type No.
Input Voltage: DC Units
AC Units
Code:
Ex d IIC T4 Ta –50ºC to +55ºC
Ex d IIC T3 Ta –50ºC to +70ºC
Ex tD A21 IP67 T135ºC based on max Ta of +55ºC
Ex tD A21 IP67 T200ºC based on max Ta of +70ºC
KEMA 00ATEX2006
Certificate No's
IECEx KEM 10.0002
Epsilon x:
Equipment Group and
Category:
CE Marking
Notified Body No.
Warnings:
DO NOT OPEN WHEN AN EXPLOSIVE
GAS OR DUST ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC
90º
Year of Construction/
Serial No.
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. IS 2492-P
INSTRUCTION MANUAL (ATEX / IECEx)
BExBG21D Flameproof Xenon Beacon
For use in Flammable Gas and Dust Atmospheres
24V or 48V
230V or 115V
II 2G/D
0518
i.e. 10 / 1DB72000001
Issue D
18-03-10
3)
Type Approval Standards
The beacon has EC Type Examination and IECEx certificates
issued by KEMA and has been approved to the following
standards:-
EN60079-0:2006 IEC60079-0:2004 (Ed4)
EN60079-1:2007 IEC60079-1:2007 (Ed6)
EN61241-0:2006 IEC61241-0:2004 (Ed1)
EN61241-1:2004 IEC60079-1:2004 (Ed1)
4)
Installation Requirements
The beacon must be installed in accordance with the latest
issues of the relevant parts of the BS EN 60079
specifications or the equivalent IEC specifications –
Selection,
Installation
apparatus for use in potentially explosive atmospheres (other
than mining applications or explosive processing and
manufacture):-
EN60079-14:2008
IEC60079-14:2007 (Ed4)
EN60079-10:2003
IEC60079-10:2008 (Ed1)
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
5)
Zones, Gas Group, Category, IP Rating and
Temperature Classification
The BExBG21D beacon has been certified Ex d IIC T3 Ta –
50ºC to +70ºC and Ex d IIC T4 Ta –50ºC to +55ºC for gas
and Ex tD IP67 T200ºC based on max Ta +70ºC and T135ºC
based on max Ta +55ºC for dust. This means that the units
can be installed in locations with the following conditions:-
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA
Group IIB
Group IIC
Temperature Classification:
sales@e-2-s.com
Sheet 1 of 4
General Requirements
Flameproof Enclosure 'd'
Dust General
Requirements
Dust Enclosures tD
and
maintenance
Electrical Installations in Hazardous
Areas (other than mines)
Classification of Hazardous Areas
Propane
Ethylene
Hydrogen and Acetylene
o
T1
400
C
Amb. +70ºC
o
T2
300
C
Amb. +70ºC
o
T3
200
C
Amb. +70ºC
o
T4
135
C
Amb. +55ºC
Tel: +44 (0)208 743 8880
www.e-2-s.com
Fax: +44 (0)208 740 4200
of
electrical
(1)

Advertisement

loading

Summary of Contents for E2S BExBG21D

  • Page 1 Certificate No’s IECEx KEM 10.0002 The BExBG21D beacon has been certified Ex d IIC T3 Ta – 50ºC to +70ºC and Ex d IIC T4 Ta –50ºC to +55ºC for gas and Ex tD IP67 T200ºC based on max Ta +70ºC and T135ºC...
  • Page 2 M6 Stainless Steel A4-80 cover bolts and their spring washer be inserted and tightened down. If the cover jams SAFETY WARNING: The BExBG21D beacon must be while it is being inserted, carefully remove it and try again. mounted with their flashdome in a position between upright Never use the cover bolts to force the cover into position.
  • Page 3 "e" or flameproof enclosure "d" and shall connected to the line. have an IP 6X rating according to EN60529:1992 SAFETY WARNING: If the BExBG21D beacon is used at SAFETY WARNING: If the BExBG21D beacon is used at high ambient temperatures, i.e. over +40ºC, then the cable high ambient temperatures, i.e.
  • Page 4 If an input and output wire is required a 2.5mm² wire can be connected to each terminal On the BExBG21D DC beacon, dc reverse line monitoring way. W hen connecting wires to the terminals great care can be used if required.