E2S E2xB05 Instruction Manual

Xenon beacons for use in hazardous locations

Advertisement

Quick Links

INSTRUCTION MANUAL
E2xB05 & E2xB10 Xenon Beacons
For use in Hazardous Locations
1) Product Table
E2xB05DC012
E2xB05DC024
E2xB05DC048
E2xB05AC115
E2xB05AC230
E2xB10DC024
E2xB10DC048
E2xB10AC115
E2xB10AC230
The current levels shown above are for the worst-case input voltage resulting in max. current.
Table 1: Electrical Ratings.
Ensure the system power supply is capable of providing the maximum current required for all units. Review associated cable
size, length and quantity of units on each circuit.
2) Warnings
 DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
 DO NOT OPEN WHEN ENERGISED
 POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
 HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
Avertissement:
 NE PAS OUVRIR UN PRESENCE
D'ATMOSPHERE EXPLOSIVE
 NE PAS OUVRIR ENERGIE
 DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
 HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L'ALIMENTATION AVANT
D'OUVRIR LA BOITIER
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D209-00-201-IS
Model
Issue 1
E2XB1X05
E2XB1X10
Nom. Voltage
12Vdc
24Vdc
48Vdc
115Vac
Nominal +/- 10%
230Vac
Nominal +/- 10%
24Vdc
48Vdc
115Vac
Nominal +/- 10%
230Vac
Nominal +/- 10%
3) Rating & Marking Information
3.1. ATEX / IECEx / UKEx certification
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7):
Explosive Atmospheres - Equipment. General Requirements
EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1):
Explosive Atmospheres - Equipment Protection by Increased
Safety "e"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2):
Explosive Atmospheres - Equipment Dust Ignition Protection
by Enclosure "t"
E2XB05 :
E2XB10 :
20-08-22
Voltage Range
10-14Vdc
20-28Vdc
42-54Vdc
20-28Vdc
42-54Vdc
Standards
Ratings
Ex ec IIC T3 Gc Ta -20°C to +40°C
Ex ec IIC T2 Gc Ta -20°C to +55°C
Ex tc IIIC 85°C Dc Ta -20°C to +40°C
Ex tc IIIC 100°C Dc Ta -20°C to +55°C
Ex ec IIC T2 Gc Ta -20°C to +55°C
Ex tc IIIC 105°C Dc Ta -20°C to +40°C
Ex tc IIIC 120°C Dc Ta -20°C to +55°C
www.e2s.com
Operating
rms Current
520mA
275mA
145mA
80mA
30mA
560mA
260mA
185mA
107mA
Tel: +44 (0)208 743 8880
Sheet 1 of 5

Advertisement

loading

Summary of Contents for E2S E2xB05

  • Page 1 INSTRUCTION MANUAL E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations E2XB1X05 E2XB1X10 1) Product Table Operating Model Nom. Voltage Voltage Range rms Current E2xB05DC012 12Vdc 10-14Vdc 520mA E2xB05DC024 24Vdc 20-28Vdc 275mA E2xB05DC048 48Vdc 42-54Vdc 145mA E2xB05AC115 115Vac Nominal +/- 10%...
  • Page 2 Explosive Atmospheres - Equipment Dust Ignition Protection by Enclosure "t" UKCA Marking Rating E2XB05: Class I Zone 2 Ex ec IIC T3 Gc Ta -20°C to +40°C 3.3. NEC & CEC Ratings Class I Zone 2 Ex ec IIC T2 Gc Ta -20°C to +55°C Zone 22 Ex tc IIIC 85°C Dc Ta -20°C to +40°C...
  • Page 3: Special Conditions Of Use

    They should only be fixed to services that can carry the weight of the unit. European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D209-00-201-IS Issue 1...
  • Page 4: Cable Connections

    0.56 Nm / 5 Lb-in. When connecting wires to the terminals great care should be taken On E2xB05/E2xB10 DC units, DC reverse line monitoring can to dress the wires so that when the cover is inserted into the be used if required.
  • Page 5 The Beacon lens cover is interchangeable, contact E2S Ltd for a replacement lens cover available in various colours. To change the lens cover, unscrew the 4-off M5 Cap screws, spring and flat washers using a 4mm Allen Key.
  • Page 6 REQUIRED MINIMUM VALUES: 24VDC : 1KΩ MIN, 2W MIN OR 3K9Ω MIN, 0.5W MIN 48VDC : 3.9KΩ MIN, 2W MIN OR 15KΩ MIN, 0.5W MIN DC XENON E2XB05 / B10 UNITS AC XENON E2XB05 / B10 UNITS Line Monitoring Power: Live & Neutral Power: +ve &...
  • Page 7: Eu Declaration Of Conformity

    Other Standards and Regulations EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/IP67 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-062_Issue_I (E2x).docx - Page 1 of 2 - QAF_252_Issue_5...
  • Page 8 This Declaration is issued under the sole responsibility of the manufacturer. Martin Streetz Document No.: DC-062_Issue_I Quality Assurance Manager Date and Place of Issue: London, 22/08/2022 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-062_Issue_I (E2x).docx - Page 2 of 2 - QAF_252_Issue_5...
  • Page 9 Other Standards and Regulations EN 60529:1992+A2:2013 ‐ Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/IP67 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-103_Issue_A - Page 1 of 2 - QAF_252_Issue_5...
  • Page 10 This Declaration is issued under the sole responsibility of the manufacturer. Martin Streetz Document No.: DC‐103_Issue_A Quality Assurance Manager Date and Place of Issue: London, 22/08/2022 E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: sales@e2s.com www.e2s.com DC-103_Issue_A - Page 2 of 2 - QAF_252_Issue_5...