Status Word
Parameter
15 14 13 12 11 10 9
Note:
The frequency inverter supports an external 24 V voltage supply for the control electronics of the fre-
quency inverter. Communication between the controlling device (PLC) and the frequency inverter is
still possible even when the mains supply has been switched off.
Bit 4 "Voltage enabled" in the Status Word indicates the current status of the mains supply.
Bit 4 "Voltage enabled" = 0 signals "no mains supply" and that starting the drive is not possible.
Bit 4 "Voltage enabled" = 1 signals "mains supply switched on" and drive ready for starting.
02/2011
411 has a length of 16 bits. The set bits have the following meaning:
8
7
Modbus Agile
Status Word
6
5
4
3
2
1
0 Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Ready to Switch On
Switched On
Operation enabled
Error
Voltage enabled
Quick Stop
Switch On disabled
Warning
-
Remote
Reference value reached
Limit value reached
-
-
-
Warning 2