9.2.1.3
Function Code 16, Write 16-Bit Parameter
Example 1:
Writing parameter
dress 3.
The rated mechanical power is to be set to 1.5 kW. Parameter
cimal place.
Thus the value to be sent is 15 = 0x000F.
Request: Master  Frequency Inverter
Field SoF Addr.
ASC
:
0
Hex
3A 30 31 31 30 34 31 37 38 30 30 30 31 30 32 30 30 30 46 32 34 0D
Response: Frequency Inverter  Master
Field SoF Addr.
ASC
:
0
Hex
3A 30 31 31 30 34 31 37 38 30 30 30 46 33 35 0D
Example 2:
Writing out of range value 0 to parameter
quency inverter with address 3.
Request: Master  Frequency Inverter
Field SoF Addr.
ASC
:
0
Hex
3A 30 33 30 36 32 31 37 38 30 30 30 31 30 32 30 30 30 30 35 33 0D
Error Response: Frequency Inverter  Master
SoF
Addr.
Field:
ASC
:
0
Hex
3A
30 31
The sent exception code is hexadecimal value 0x04 = SLAVE DEVICE FAILURE.
02/2011
Rated Mech. Power
376 (0x0178) in data set 4 to the frequency inverter with ad-
Fct.Co
DSet/Par-No.
de
1
1
0
4
1
7
Fct.Co
DSet/Par-No.
de
1
1
0
4
1
7
Fct.Co
DSet/Par-No.
de
1
1
0
2
1
7
Except.
Fct.Code
Code
1
9
0
0
39
30
30 34 36 42 0D 0A
Rated Mech. Power
No.
No. Registers
Byte
8
0
0
0
1
0
Para-Value
LRC
8
0
0
0
F
3
Rated Mech. Power
376 (0x0178) in data set 2 of the fre-
No.
No. Registers
Byte
8
0
0
0
1
0
LRC
EoF
4
6
B
CR LF
Modbus Agile
376 has one de-
Para-Value
LRC
2
0
0
0
F
2
EoF
5
CR
LF
0A
Para-Value
LRC
2
0
0
0
0
5
EoF
4
CR
LF
0A
EoF
3
CR
LF
0A
55