9
Modbus Message Examples
This chapter describes some examples for Modbus RTU and Modbus ASCII.
9.1
Modbus RTU-Message Examples
9.1.1
16 Bit Parameter access
9.1.1.1
Function Code 3, Read 16-Bit Parameter
Example 1:
Reading parameter
1.
Request: Master Frequency Inverter
Field:
Addr.
Hex
01
Response: Frequency Inverter Master
Field:
Addr.
Hex
01
The hexadecimal value sent is 0x056E = 1390. Parameter
Therefore, the rated speed is 1390 min
Example 2:
Reading parameter
1 and No. of Regs field set to 2 (invalid value).
Request: Master Frequency Inverter
Field:
Addr.
Hex
01
Error Response: Frequency Inverter Master
Field:
Addr.
Hex
01
The exception code sent is hexadecimal value 0x04 = SLAVE DEVICE FAILURE.
02/2011
Rated Speed
372 (0x0174) in data set 2 from the frequency inverter with address
Func.
DSet/Par-No.
03
21
74
Func.
No.Bytes
Par-Value
03
02
05
-1
.
Rated Speed
372 (0x0174) in data set 0 from the frequency inverter with address
Func.
DSet/Par-No.
03
01
74
Func.
Except.
CRC
83
04
40
No. of Regs
CRC
00
01
CE
CRC
6E
3A
F8
Rated Speed
No. of Regs
CRC
00
02
85
F3
Modbus Agile
2C
372 has no decimal places.