9.1.2
32 Bit Zugriff
9.1.2.1
Function Code 3, Read 32-Bit Parameter
Example 1:
Reading parameter
address 1.
Request: Master Frequency Inverter
Field:
Addr.
Hex
01
Response: Frequency Inverter Master
Field:
Addr.
Hex
01
The hexadecimal value sent is 0x03E8 = 1000. Parameter
places.
Therefore, the frequency is 10.00 Hz.
Example 2:
Reading parameter
address 1 and No. of Regs field set to 1 (invalid value).
Request: Master Frequency Inverter
Field:
Addr.
Hex
01
Error Response: Frequency Inverter Master
Field:
Addr.
Hex
01
The exception code sent is hexadecimal value 0x04 = SLAVE DEVICE FAILURE.
48
Fixed Frequency 2
481 (0x01E1) in data set 1 from the frequency inverter with
Func.
DSet/Par-No.
03
11
E1
Func.
No.Bytes
03
04
00
Fixed Frequency 2
481 (0x01E1) in data set 0 from the frequency inverter with
Func.
DSet/Par-No.
03
01
E1
Func.
Except.
CRC
83
04
40
No. of Regs
CRC
00
02
91
Par-Value
00
03
E8
Fixed Frequency
No. of Regs
CRC
00
01
D5
F3
Modbus Agile
Modbus Message Examples
01
CRC
FA
8D
481 has two decimal
C0
02/2011