BONFIGLIOLI Vectron Agile Communications Manual page 47

Modbus communication. frequency inverter 230v / 400v.
Hide thumbs Also See for Agile:
Table of Contents

Advertisement

9.1.1.3
Function Code 16, Write 16-Bit Parameter
Example 1:
Writing parameter
dress 1.
The rated mechanical power is to be set to 1.5 kW. Parameter
cimal place.
Therefore the value to be sent is 15 = 0x000F.
Request: Master  Frequency Inverter
Field:
Addr.
Hex
01
Response: Frequency Inverter  Master
Field:
Addr.
Hex
01
The response contains the no. of registers written.
Example 2:
Writing out of range value 0 to parameter
quency inverter with address 1.
Request: Master  Frequency Inverter
Field:
Addr.
Hex
03
Error Response: Frequency Inverter  Master
Field:
Addr.
Hex
03
The exception code sent is hexadecimal value 0x04 = SLAVE DEVICE FAILURE.
02/2011
Rated Mech. Power
376 (0x0178) in data set 4 to the frequency inverter with ad-
Func.
DSatz/Par-Nr.
10
41
78
Func.
DSet/Par-No.
10
41
78
Func.
DSatz/Par-Nr.
10
41
78
Func.
Except.
CRC
90
04
EC
Rated Mech. Power
No. of
No. of registers
bytes
00
01
02
No. of registers
00
01
95
Rated Mech. Power
376 (0x0178) in data set 2 to the fre-
No. of
No. of registers
bytes
00
01
02
03
Modbus Agile
376 has one de-
Par-value
CRC
00
0F
BD
CRC
EC
Par-value
CRC
00
00
E4
28
4C
47