BONFIGLIOLI Vectron Agile Communications Manual page 46

Modbus communication. frequency inverter 230v / 400v.
Hide thumbs Also See for Agile:
Table of Contents

Advertisement

9.1.1.2
Function Code 6, Write 16-Bit Parameter
Example 1:
Writing parameter
dress 3.
The rated mechanical power is to be set to 1.5 kW. Parameter
cimal place.
Therefore the value to be sent is 15 = 0x000F.
Request: Master  Frequency Inverter
Field:
Addr.
Hex
03
Response: Frequency Inverter  Master
Field:
Addr.
Hex
03
The response is an echo of the request message.
Example 2:
Writing out of range value 0 to parameter 376 (0x0178) in data set 2 to the frequency inverter with
address 3.
Request: Master  Frequency Inverter
Field:
Addr.
Hex
03
Error Response: Frequency Inverter  Master
Field:
Addr.
Hex
03
The exception code sent is hexadecimal value 0x04 = SLAVE DEVICE FAILURE.
46
Rated Mech. Power
376 (0x0178) in data set 4 to the frequency inverter with ad-
Funk.
DSatz/Par-Nr.
06
41
78
Func.
DSet/Par-No.
06
41
78
Func.
DSet/Par-No.
06
21
78
Func.
Except.
CRC
86
04
E2
Rated Mech. Power
Par-Wert
CRC
00
0F
5C
Par-Value
CRC
00
0F
5C
Par-Value
CRC
00
00
02
63
Modbus Agile
Modbus Message Examples
376 has one de-
09
09
0D
02/2011