16 | Water Quality
NOTICE: Water side pressure rating is 450
psi for FPT fittings and 125 psi for field or
factory installed swivel fittings.
NOTICE: Do not overtighten the
connections.
Flexible hoses should be used between the unit and the
rigid system to avoid possible vibration. Ball valves
should be installed in the supply and return lines for unit
isolation and unit water flow balancing.
WATER QUALITY
Table 1: Water Quality
POTENTIAL
PROBLEM
SCALING
CORROSION
IRON FOULING
EROSION
* No "rotten egg" smell present at < 0.5 ppm H2S.
** Equivalent to 30 mesh strainer
8733942411 (2017/07)
Water Characteristic
pH (Acidity/Alkalinity)
Hardness (CaCO3,
MgCO3)
Ryznar Stability Index
Langelier Saturation Index
Hydrogen Sulfide (H2S)
Sulfates
Chlorine
Chlorides
Carbon Dioxide
Ammonia
Ammonia Chloride
Ammonia Nitrate
Ammonia Hydroxide
Ammonia Sulfate
Dissolved Solids
Iron (Fe2+ Iron Bacteria
Potential)
Iron Oxide
Suspended Solids
Maximum Water Velocity
Subject to change without prior notice
Acceptable Value
Copper
7-9
< 350 ppm
6.0 - 7.5
-0.5 - +0.5
< 0.5 ppm *
< 125 ppm
< 0.5 ppm
< 20 ppm
< 50 ppm
< 2 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 1,000 ppm
< 0.2 ppm
< 1 ppm
< 10 ppm, < 600 μm size **
6 ft/sec
SM Series Heat Pump
Cupro-Nickel
7-9
< 350 ppm
6.0 - 7.5
-0.5 - +0.5
10-50 ppm
< 125 ppm
< 0.5 ppm
< 150 ppm
< 50 ppm
< 2 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 1,500 ppm
< 0.2 ppm
< 1 ppm
< 10 ppm, < 600 μm size **
6 ft/sec
SM Series Heat Pump

Advertisement