Installation Instructions

13.8 Parameter Point Check Table

To display system parameters, press the "Check" button to
index through the series of parameters available. The first time
you press the "Check" button, it will display the sequence,
and after 1 second it will display the value of the parameter.
If you press the "Check" button again, it will display the next
sequence. Refer to Figure 32 for check button location on the
control board.
SW2
CHECK
Figure 30
No.
Point check content
0
Outdoor unit capacity
1
Outdoor unit mode
2
Outdoor unit set compressor speed(Hz)
3
T3(outdoor coil temp.) °F
4
T4 (outdoor ambient temp.) (°F )
5
T5 (compressor discharge temp.) (°F )
6
T6 (compressor suction temp.) (°F )
7
T7(liquid line temp.) °F
8
Tf (module temp.) (°F )
9
Pe (evaporating pressure) (PSI)
10
Pc (condensing pressure) (PSI)
11
Tes target of the evaporating temp. (only use for cooling mode) (°F )
12
Te (evaporating temp.) (°F )
13
Tcs target of the condensing temp. (only use for heatling mode) (°F )
14
Tc (condensing temp.) (°F )
15
Target of the compressor discharge superheat (only use for heating mode) (°F )
16
Compressor discharge superheat (°F )
17
Opening of EEV
18
Fan speed
19
Compressor current (A)
20
Alternating voltage
21
Compressor input dc voltage
22
Continuous running time of the compressor
23
Last Fault Code
24
Software version
25
T1 (Return air temp) (°F )
26
T2 (Indoor coil temp) (°F )
27
Indoor blower motor speed
28
Ts (Estimated thermostat set point) (°F )
29
Remark"--"
Table 22
3 0 |
Normal Status, last two digits will display under the following
conditions
i. Unit not operating (Standby Mode); "outdoor ambient
temperature".
ii. Unit operating; displays "compressor operating frequency".
After 20 seconds on same parameter, the display will revert
back to normal status.
If a system protection is active, first digit will display "status
code".
Bosch 15 SEER2 Inverter Ducted Packaged Heat Pump - BTC 761701319 A (12.2022)
Example
Remark
RH5
RH5=Heat pump 5 ton
0 Standby,
2
2 cooling,
3 Heating
66
66 Hz
108
108 °F
95
95 °F
140
140 °F
55
55 °F
99
99 °F
120
120 °F
140
140 psi
380
380 psi
43
43 °F
43
43 °F
106
106 °F
106
106 °F
36
36 °F
36
36 °F
200
200 p(0~480)
9
9 speed
10
10 A
230
230 V
380
380 V
35
35 min
00
see table 9-4 (*UPDATE*)
01
V1.0
70
70°F
50
50°F
4
4 speed
70
70°F
--
--