83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
Ratings apportionment
The load points are automatically assigned relative to the capacity. Incorrect load
distribution can cause operating problems during the load control.
Assign capacity in % for load point using the following formula.
Enter the calculated capacity for load point in Load.
Load [%] =
Select Point and confirm with [ENTER].
Select load point using dial knob and confirm with [ENTER] key.
Confirm query Change point? with [ENTER].
Confirm query With start with [ENTER].
Confirm line Load with [Enter].
Calculate actual load.
Set load using dial knob and confirm with [Enter].
Exit point using [esc] and save with [ENTER].