83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
5. Limit external setpoint
It is possible to define limits for the setpoint for the operating mode with external
setpoint.
With an analogue setpoint signal the limit value relates to the measuring range set
[ch. 6.12.6].
Select Ext MinSetpoint or Ext MaxSetpoint .
Set the limit value using the dial knob and confirm with [Enter].
Use [esc] to return to the menu.
6. Determine internal setpoint
Two setpoints can be set for the operating mode with internal load controller
[ch. 6.12.1].
Select LoadController.
Select ControlParam.
Select SetpointW1 .
Set setpoint using the dial knob and confirm with [Enter].
Use [esc] to return to the display ControlParam.
If the second setpoint W2 is required:
Repeat procedure for SetpointW2.
7. Set temperature sensor function
With an activated temperature monitor, the switch threshold and switch-on hyster-
esis can be set [ch. 6.12.13].
Select LoadController.
Select TempLimiter.
Select TL_ThreshOff.
Set threshold using the dial knob and confirm with [Enter].
Use [esc] to return to the display TL_ThreshOff .
Select TL_SD_On.
Set switch-on hysteresis using the dial knob and confirm with [Enter].
Use [esc] to return to the display TempLimiter.
177-228
7 Commissioning