Weishaupt W-FM 100 Installation And Operating Instruction page 205

Combustion manager
Table of Contents

Advertisement

Fault
Diagnostic
Cause
codes
code
33
Unexpected oil pressure, min. oil pressure
switch has triggered, contact closed
34
Min. oil pressure switch has not reacted, con-
tact open
35
Max. oil pressure switch has triggered, con-
tact closed
36
No signal at input start release Oil [ch. 3.3.9]
37
No signal at input heavy oil immediate start
[ch. 3.3.10]
38
Low gas programme activated
39
Internal safety time error
3A
No burner identification is saved in the
W-FM.
3B
No HE password defined
40
Internal safety relay fault
41
Internal ignition contact setting fault
42
01 ... FF
Internal fuel valve relay contact setting fault
01
Anti syphon valve / safety valve Oil SV
X6-03*
02
Fuel valve Oil V1 X8-02 / X8-03
04
Fuel valve Oil V2 X7-01
08
Fuel valve Oil V3 X7-02
10
External solenoid valve Gas / safety valve Gas
SV X9-01:1
20
Fuel valve Gas V1 X9-01:4
40
Fuel valve Gas V2 X9-01:3
80
Ignition gas valve PV X9-01:2
43
01
No fuel or both selected via input X4-01
02
Fuel supply without compound curves
03
Variable "Supply" not defined
04
Variable "Fuel" not defined
05
Undefined operating mode with load control-
ler
06
Pre-purge time Gas too short
07
Pre-purge time Oil too short
08
Safety time 1 Gas too long
09
Safety time 1 Oil too long
0A
Time ignition Off greater than safety time 1
Gas
0B
Time ignition Off greater than safety time 1
Oil
0C
Safety time 2 Gas too long
0D
Safety time 2 Oil too long
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.
83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
205-228
Rectification
Check pump pressure.
Check oil supply
Check min. oil pressure switch.
Check gas connection pressure
Transfer data from the ABE [ch. 6.16.1].
Check electrical connection at output.
If several faults occur, the diagnosis codes
are add up.
Check electrical connection at output.
Depending on the operating phase an imper-
missible voltage signal is present at the cor-
responding output. This could be triggered by
reverse voltage caused by an operating signal
(e. g. during a lamp test).
Check electrical connection [ch. 6.4.2].
Set fuel.
Transfer data from the ABE [ch. 6.16.1].
Check fuel selection [ch. 6.4.2].
Check operating mode [ch. 6.12.2].
(1
Internal fault
9 Troubleshooting