Combustion manager
Table of Contents

Advertisement

83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
Param & Display (continued)
Process data
CombEfficiency
Man Var O2Ctrl
State O2Ctrl
Air-Related Load
Diag Reg State
Load controller
Controller parameters
ContrlParamList
StandardParam
P Part (Xp) [15 %]
I Part (Tn) [320 s]
D Part (Tv) [40 s]
MinActuatorStep [1 %]
SW_FilterTmeCon [3 s]
SetpointW1
SetpointW2
Sd_ModOn [1 %]
Sd_ModOff [10 %]
Sd_Stage1On [-2 %]
Sd_Stage1Off [10 %]
Sd_Stage2Off [8 %]
Sd_Stage3Off [6 %]
ThreshStage2On[300]
ThreshStage3On [600]
(2
TempLimiter
TL_ThreshOff [95 °C]
TL_SD_On [-5 %]
Cold start
ColdStartOn
ThresholdOn
StageLoad
StageSetp_Mod
StageSetp_Stage
MaxTmeMod
MaxTmeStage
ThresholdOff
AdditionalSens
Temp. ColdStart
SetpAddSensor
Release Stages
Configuration
LC_OptgMode [Int LR]
Sensor Select
MeasureRangePtNi
var.RangePtNi
Ext Inp X61 U/I
MRange TempSens
MRange PressSens
Ext Inp X62 U/I
Ext MinSetpoint
Ext MaxSetpoint
(1
W-FM 200 only
(2
only with HE password
61-228
(2
[deactivated]
(2
[20 %]
(2
[15 %]
(2
[5 %]
(2
[5 %]
(2
[3 min]
(2
[3 min]
(2
[80 %]
(2
[deactivated]
(2
(2
[Release]
(2
[Pt100]
(2
[150 °C / 302 °F]
(2
[850 °C]
(2
[0 ... 10 V]
(2
[90 °C]
(2
[2 bar]
(2
[4 ... 20 mA]
(2
[0 %]
(2
[60 %]
6 Operation