Weishaupt W-FM 100 Installation And Operating Instruction page 209

Combustion manager
Table of Contents

Advertisement

Fault
Diagnostic
Cause
codes
code
A0
01 ... 1F
Auxiliary actuator3 has signalled a fault
01
CRC error during ROM test
02
CRC error during RAM test
04
Error in key value test
05
Time block overrun
07
Synchronisation or CRC error
08
Cycle counter error
09
Error during stack test
0C
Temperature in the actuator too high
0D
Rotational direction of actuator incorrect
0E
Ramp time for path insufficient
10
Timeout during analogue to digital conversion Internal fault
11
Error during test analogue to digital converter
12
Error during analogue to digital conversion
13
Actuator position outside of permissible
range (0 ... 90°)
15
CAN-Bus connection error
16
CRC error of parameter page
17
Page was open too long
18
Page has been corrupted
19
Invalid access to parameters
1B
Error when copying a parameter page
1E
Invalid position range in drive command
1F
Internal plausibility fault
A1
See A0
Air actuator has signalled a fault
A2
See A0
Fuel actuator Gas has signalled a fault
A3
See A0
Fuel actuator Oil has signalled a fault
A4
See A0
Auxiliary actuator1 has signalled a fault
A5
See A0
Auxiliary actuator2 has signalled a fault
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.
83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
209-228
Rectification
Check CAN Bus and Bus connection
[ch. 5.1].
(1
Internal fault
Check housing temperature (max. 60°C), if
necessary supply with cooling air.
Check mechanics after the actuator for
freedom of movement.
Check rotation direction, change if re-
quired (OEM level).
Check actuator ramp time [ch. 6.9.1].
Ramp time should not be less slowest ac-
tuator
Reduce path between special positions.
(1
Check actuator position, if necessary turn
back mechanically.
Check CAN Bus connection [ch. 5.1].
Reset W-FM, see [ch. 9.1].
If the error occurred during a parameter
change:
Check parameter that was last changed for
plausibility.
If the reset does not achieve a fault free con-
dition:
Load data from the ABE [ch. 6.16.1].
If none of the actions listed leads to a fault
free condition:
Replace W-FM.
Check SpecialPositions.
Valid position range: 0 ... 90°
Optimise EMC measures.
See A0
See A0
See A0
See A0
See A0
9 Troubleshooting