5. Set setpoint step
For modulating operation:
Select StageSetp_Mod.
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display StageSetp_Mod.
For multi-stage operation:
Select StageSetp_Stage.
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display StageSetp_Stage.
6. Set residence time
For modulating operation:
Select MaxTmeMod .
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display MaxTmeMod.
For multi-stage operation:
Select MaxTmeStage.
Set setpoint step using the dial knob and confirm with [Enter].
Use [esc] to return to the display MaxTmeStage.
7. Carry out data backup
Exit level using the [esc] key.
The display shows Create parameter backup?.
Start data backup by pressing [ENTER] key.
The display shows Parameters are being updated and the Para-
meters have been saved.
The values have been backed up from the combustion manager to the ABE.
Exit level using the [esc] key.