Combustion manager
Table of Contents

Advertisement

6 Operation
83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
Operation (continued)
O2 module
curr. O2 value
O2 setpoint
Inlet air temperature
Flue gas temperature
CombEfficiency
Burner identification
Operating mode selection
Interface PC
GatewayBASon
GatewayBASoff
Type of Gateway [Modbus]
O2Ctrl activate
Manual operation
SetLoad
Autom/Manual/Off [Automatic]
Param & Display
Burner Control
(2
Times
TimeStartup1
MinTimeStartRel [1 s]
FanRunUpTme [2 s]
PrepurgeTmeGas [20 s]
PrepurgeTmeOil [15 s]
PrepurgeSafeGas [20 s]
PrepurgeSafeOil [15 s]
PrepurgePtl1Gas [0.2 s]
PrpurgePt3Gas [0.2 s]
PrepurgePt1Oil [0.2 s]
PrepurgePt3Oil [0.2 s]
PreIgnTime_Gas [2 s]
PreIgnTime_Oil [2 s]
MinOnTime Oil pump [1 s]
TimeStartup2
Interval1Gas [2 s]
Interval1Oil [2 s]
Interval2Gas [2 s]
Interval2Oil [2 s]
PressReacTime [2 s]
TimeShutdown
MaxTmeLowFire [45 s]
AfterburnTme [8 s]
PostpurgeT1Gas [0.2 s]
PostpurgeT1Oil [0.2 s]
PostpurgeT3Gas [5 s]
PostpurgeT3Oil [5 s]
PostpurgeT3long [0 s]
DelayLackGas [10 s]
(1
W-FM 200 only
(2
only with HE password
58-228
(1
(1
(1
(1
(1
(1
(1