Weishaupt W-FM 100 Installation And Operating Instruction page 127

Combustion manager
Table of Contents

Advertisement

83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
Output values
Defines the internal value (%, °C, bar or degree of angle) at which 20 mA flow at
output X63.
Setting
Scale20mA prec
Scale20mA temp
Press X61
Scale20mA angle
Scaling (Scale 0/4mA)
Parameter Scale 0/4mA defines the internal value for the lower current limit.
Depending on parameter CurrMode 0/4mA 4 mA or 0 mA flow at the value set.
The relative value in percent refers to the output value set (Scale20mA ... /
Press X61).
127-228
Function
Internal percentage value (0 ... 999.9 %) at 20 mA, valid
for:
Load 0
O2
Speed VSD
Flame
Temperature at input X60/X61 (0 ... 2000 °C) at 20 mA,
valid for:
Temp Pt1000 / Temp Ni1000 / Temp Pt100
Temp X61
Pressure sensor at input X61 (0 ... 99.9 bar) at 20 mA,
valid for Press X61.
Actuator position in degree of angle (0 ... 90°) at 20 mA,
valid for:
Pos Air
Pos fuel
Pos Aux...