Weishaupt W-FM 100 Installation And Operating Instruction page 211

Combustion manager
Table of Contents

Advertisement

Fault
Diagnostic
Cause
codes
code
A6
50 ... 5A
Load controller input error
50
Short circuit at input X60:1/4
51
Break at input X60:1/4
52
Break at input X60:2/4
53
Short circuit at input X60:3/4
54
Break at input X60:3/4
55
Short circuit at input X60:3/4
56
Break at input X60:3/4
57
Excess voltage at input X61
58
Break or short circuit at input X61
59
Excess voltage at input X62
5A
Break or short circuit at input X62
A6
5B
The output value is not available for output
X63 in the current configuration.
A6
5C
FGR sensor is not available in the current
configuration.
A6
60 ... 6F
Internal load controller fault
A6
70 ... 77
Load controller input signals fluctuate too
much
70
Signal fluctuation input X60:1/4
71
Signal fluctuation input X60:2/4
72
Signal fluctuation input X60:3/4
73
Signal fluctuation PWM
74
Signal fluctuation U-input X61:2
75
Signal fluctuation I-input X61:3
76
Signal fluctuation U-input X62:2/4
77
Signal fluctuation I-input X62:3/4
A6
78 ... 7F
Load controller input signals too great or in-
correct polarity.
78
Excess voltage or incorrect polarity input
X60:1/4
79
Excess voltage or incorrect polarity input
X60:2/4
7A
Excess voltage or incorrect polarity input
X60:3/4
7B
Excess voltage or incorrect polarity PWM
7C
Excess voltage or incorrect polarity input X61
7D
Current flow is too high or incorrect polarity
input X61
7E
Excess voltage or incorrect polarity input X62
7F
Current flow is too high or incorrect polarity
input X62
A6
80 ... A6
Internal load controller fault
A6
A7
Incorrect or no additional sensor for boiler
cold start function defined.
A6
B0 ... FF
Internal load controller fault
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.
83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
211-228
Rectification
The diagnostic code indicates which input is
affected.
Check electrical connection and sensor.
Change setting [ch. 6.12.7].
Change setting [ch. 6.15.3].
(1
Internal fault
The diagnostic code indicates which input is
affected [ch. 3.3.20].
Check electrical connection
Check signal (ripple voltage).
The diagnostic code indicates which input is
affected [ch. 3.3.20].
Check electrical connection
Check voltage or current.
(1
Internal fault
Change setting [ch. 6.12.14].
(1
Internal fault
9 Troubleshooting