9 Troubleshooting
Fault
Diagnostic
Cause
codes
code
AB
01 ... 3F
O
01 ... 0A
Internal O
10
Nernst voltage of O
missible range
12
Voltage thermocouple of O
permissible range
13
Voltage temperature compensation of O
sensor outside of permissible range
15
Temperature combustion air sensor outside
of permissible range (-20 ... +800°C)
16
Temperature flue gas temperature sensor
outside of permissible range
(-20 ... +800°C)
17 ... 1F
Internal fault O
20
Sensor temperature of O
21
Sensor temperature of O
22
Errors during calculation test
23
Internal resistance of O
or greater than 150 Ω
24
Reaction time of O
5 seconds
25
Error during sensor test [ch. 6.10.22]. O
value fluctuates, flow too low.
30
CAN-Bus connection error
31
CRC error of parameter page
32
Page was open too long
33
Page has been corrupted
34
Invalid access to parameters
38
Error when copying a parameter page
3E
Invalid external default
3F
Internal plausibility fault
B0
01, 02
Fault during output test
B1
01
Error in short circuit testing of inputs to out-
puts
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.
83054802 1/2018-07 La
Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
module has signalled a fault
2
module fault
2
sensor outside of per-
2
module in test phase
2
sensor too low
2
sensor too high
2
sensor less than 5 Ω
2
sensor greater than
2
Rectification
Internal fault
Check electrical connection [ch. 3.3.25].
sensor outside of
2
2
Check electrical connection and sensor
[ch. 6.10.9].
Check temperature.
Internal fault
Check voltage supply and unit fusing of in-
ternal O
Check voltage supply sensor heating (Q4/
Q5) [ch. 3.3.25].
Check sensor temperature [ch. 6.10.20].
Internal fault
Check electrical connection [ch. 3.3.25].
Replace O
Check installation position of O
[ch. 4.1].
Clean O
2
Replace O
If necessary increase O
Check CAN Bus and Bus connection
[ch. 5.1].
Internal fault
Reset W-FM, see [ch. 9.1].
If the error occurred during a parameter
change:
Check parameter that was last changed for
plausibility.
If the reset does not achieve a fault free con-
dition:
Load data from the ABE [ch. 6.16.1].
If none of the actions listed leads to a fault
free condition:
Replace W-FM.
Internal fault
Internal fault
Internal fault
214-228
(1
(1
module.
2
(1
sensor [ch. 6.10.22].
2
sensor
2
sensor.
2
sensor (sensor ageing).
2
control limit.
2
(1
(1
(1
(1