Operation
40.YCDO
41.YCUP
42.BIN1
43.BIN2
86
Value for sealing bottom
When the sealing function bottom (see parameter"39.YCLS"is activa-
ted, it can be set below which setpoint the bottom sealing is activated
with this parameter.
Value for sealing top
When the sealing function top (see parameter"39.YCLS"is activated, it
can be set above which setpoint the top sealing is activated with this
parameter.
Function digital input 1 (see figure 4-6, page 79)
and
Function digital input 2 (see figure 4-6)
The parameters "42.BIN1" and "43.BIN2" can be set individually depen-
ding on the purpose. The direction of action can be adapted to an NCC
or an NOC.
- BIN1 or BIN2 = on or --on
Digital messages of the periphery (e.g. pressure or temperature
switches) can be read out via the HART interface or lead to respon-
ding of the fault message output by OR linking with other messages.
- BIN1 = bLc1
The Configuration operating level is locked to prevent it being adju-
sted (e.g. by a wire jumper between terminals 9 and 10).
- BIN1 = bLc2
If digital input 1 has been activated, manual operation is also locked
in addition to the Configuration operating level.
- BIN1 or BIN2 = uP or doWn (contact closes) or --uP or --doWn (con-
tact opens).
The actuator drives the linear actuator to the upper or lower stop
when the digital input is activated with continuous contact.
- BIN1 or BIN2 (contact closes) = StoP or --StoP (contact opens).
With activated digital input the piezo--valves are blocked and the
actuator remains in the last position. Leakage messages can then
be executed without initialization function.
- BIN1 or BIN2 = oFF (factory setting)
no function
special function of DI1: If the digital input 1 is activated in P manual
operation by a jumper between terminals 9 and 10, "NOINI" or the
100times input current in mA is displayed alternately in the bottom
line of the display.
If one of the above named functions is selected with the parameters
"42.BIN1" and "43.BIN2" simultaneously, then "Blocking" has priority
over "Up" and "Up" priority over "Down".
SIPART PS2 Manual
A5E00074631-01