For almost all models the PLC communication setting method is as follows. However, differences
may arise depending on the model. For details, please consult the manual for the PLC you will
use when making the settings.
To communicate using the RS232C port of the CPU unit
Set the system area as follows.
Address
Value set
DM6600
0201 (HEX)
DM6645
0001 (HEX)
DM6646
0004 (HEX)
DM6648
0000 (HEX)
To communicate using the communication port
Set the system area as follows.
To communicate with port A
Address
Value set
DM6600
0201 (HEX)
DM6550
0001 (HEX)
DM6551
0004 (HEX)
To communicate with port B
Address
Value set
DM6600
0201 (HEX)
DM6555
0001 (HEX)
DM6556
0004 (HEX)
To communicate using the high link I/F unit
Make sure set the CPU mode to monitor mode.
Use the DIP switch or rotary switch on the link I/F unit to make settings such as the baud rate.
For details please refer to the manual for the unit your are using.
To communicate using the peripheral port
Set the system area as follows.
Address
Value set
DM6600
0201 (HEX)
DM6550
0001 (HEX)
DM6551
0004 (HEX)
Usable devices
Device type
Relay area
Data memory area
Note1) Depending on the type being used, the address range may be limited to a small range. Refer to
the instruction manual of the PLC being used for detailed information.
Note2) Data cannot be written to relay areas 253 to 255CH.
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
Setting of device number (Device No. 0)
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
0000CH to 0252CH
DM0000 to DM6143
Setting
Setting
Setting
Setting
Address range
Points
253 words
6143 words
4-61