9.5 MODBUS MEMORY MAPPING
Table 9–3: DGP MODBUS MEMORY MAP (Sheet 24 of 24)
ADDRESS
ITEM NAME
DEC
HEX
22274
5702
81-4O SETPNT
22275
5703
81-4O TL18
22528
5800
DIG INP SELBKD11
22529
5801
DI3 TRIP
22530
5802
DI3 ALARM
22531
5803
DI3 TIMER
22532
5804
DI4 TRIP
22533
5805
DI4 ALARM
22534
5806
DI4 TIMER
22535
5807
DI6 FUNC
22784
5900
VTFF
23040
5A00
AE TRIP
23041
5A01
AE ALARM
23042
5A02
AE ARM
23296
5B00
51GN TRIP
23297
5B01
51GN ALARM
23298
5B02
51GN PICKUP
23299
5B03
51GN TIME FAC
23552
5C00
27 TRIP
23553
5C01
27 ALARM
23554
5C02
27 PICKUP
23555
5C03
27 TIME FAC
23556
5C04
27 CURVE #
23808
5D00
27TN TRIP
23809
5D01
27TN ALARM
23810
5D02
27TN PICKUP
23811
5D03
27TN TL20
23812
5D04
27TN FORPWR_L
23813
5D05
27TN FORPWR_H
9
GENERATOR AND STATION ID
32256
7E00
STATION ID
32288
7E20
GENERATOR ID
9-
48
DGP Digital Generator Protection System
9 COMMUNICATIONS
UNITS
FORMAT
HZ
INT2
SEC
INT2
INTO
SP
SP
SEC
INT2
SP
SP
SEC
INT2
BOOLEAN
BOOLEAN
SP
SP
BOOLEAN
SP
SP
AMP
INT2
SEC
INT2
SP
SP
VOLT
INTO
SEC
INT2
INTO
SP
SP
VOLT
INT1
SEC
INT1
WATT
INTO
WATT
INTO
ASCII
ASCII
GE Power Management
NO. OF
REGISTERS
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
32