9 COMMUNICATIONS
9.6 COIL COMMANDS
The following coil commands are accepted by the DGP relay. Multiple commands are not supported. They can
be executed only by the function code 05H. Both the hexadecimal and decimal coil addresses are offset.
Table 9–4: COIL COMMANDS
ADDRESS
COIL COMMAND
DEC
HEX
0
0
END COMMAND*
1
1
ENABLE OUTPUT
1
1
DISABLE OUTPUT
2
2
RESET FAULT
3
3
RESET EVENTS
4
4
RESET TARGET
100
64
END RELAY TEST
101
65
RELAY TEST 87G
102
66
RELAY TEST 46A
103
67
RELAY TEST 46T
104
68
RELAY TEST 40-1
105
69
RELAY TEST 40-2
106
6A
RELAY TEST 32-1
107
6B
RELAY TEST 32-2
108
6C
RELAY TEST 51V
109
6D
RELAY TEST 64G1
110
6E
RELAY TEST 64G2
111
6F
RELAY TEST 24A
112
70
RELAY TEST 24T
113
71
RELAY TEST 59
114
72
RELAY TEST 81-1U
115
73
RELAY TEST 81-2U
116
74
RELAY TEST 81-3U
117
75
RELAY TEST 81-4U
* END COMMAND must be sent after new settings are sent to the DGP.
GE Power Management
Table 9–4: COIL COMMANDS
DGP Digital Generator Protection System
9.6 COIL COMMANDS
ADDRESS
COIL COMMAND
DEC
HEX
118
76
RELAY TEST 81-1O
119
77
RELAY TEST 81-2O
120
78
RELAY TEST VTFF
121
79
RELAY TEST AE
122
7A
RELAY TEST 51GN
123
7B
RELAY TEST 27
124
7C
RELAY TEST 27TN
200
C8
END DO TEST
201
C9
DO TEST 94G
202
CA
DO TEST 94G1
203
CB
DO TEST 94G2
204
CC
DO TEST 94G3
205
CD
DO TEST 74A
206
CE
DO TEST 74B
207
CF
DO TEST 74C
208
D0
DO TEST 74D
209
D1
DO TEST 74CR
210
D2
DO TEST 74NC
211
D3
DO TEST 74FF
300
12C
TRIB BRKR 94G
301
12D
TRIB BRKR 94G1
302
12E
TRIB BRKR 94G2
303
12F
TRIB BRKR 94G3
9.6.1 DESCRIPTION