E54.4
Incorrect transfer of data
from the charger of
battery 2
E54.5
No bus communication
with the printed circuit
board of slave control
E62.0
Low water level
E64.0
Room temperature
under 10 °C
E100.1
Battery 1 malfunction
E100.2
Battery 2 malfunction
E105.1
Short-circuit battery 1
E105.2
Short-circuit battery 2
E106.1
Cable rupture battery 1
E106.2
Cable rupture battery 2
E130.0
Insufficient fuel
E131.0
Heating malfunction
E132.0
Low oil pressure
E133.0
Excessive motor
temperature
E134.0
Pinion of the non-
engaged starter
E135.0
Pinion circuit interrupted
E136.0
Start-up failure
E137.0
Belt rupture
WILO SE 11/2016
Malfunction on the data line
Connection with the printed
circuit board of slave control
interrupted
Software integrity error
Level below minimum filling
level in the storage tank
Leakage
Room not heated
Battery 1 defective
Battery 2 defective
Battery 1 defective
Battery 2 defective
Connection with battery 1
interrupted
Connection with battery 2
interrupted
Fuel level lower than the
minimum
The heating thermostat is
triggered
The oil pressure switch is
triggered
The motor thermostat is
triggered
No response from starter
pinion
No response from starter
pinion
6 failed start-up attempts
No alternator voltage
Request customer service
Check connection
Request customer service
Filling the storage tank
Check the impermeability of
the storage tank and of the
core
Heat the room
Check battery 1 and replace
it if necessary
Request customer service
Check battery 2 and replace
it if necessary
Request customer service
Check battery 1 and replace
it if necessary
Request customer service
Check battery 2 and replace
it if necessary
Check the connection of
battery 1
Request customer service
Check the connection of
battery 2
Request customer service
Add fuel
Check heating
Check the oil level and fill it if
required
Request customer service
Check the level of the
cooling water
Request customer service
Check the starter
Check the fuse
Request customer service
Check the fuse
Request customer service
Request customer service
Check the V-belt and
replace it in necessary
English
50