Installation; Mounting Of Compressor; Ventilation And Cooling; Service Air Piping - Sullair LS-10 25HP Operators Manual And Parts Lists

Industrial air compressor
Table of Contents

Advertisement

4.1 MOUNTING OF COMPRESSOR

A foundation or mounting capable of supporting
the weight of the compressor, and rigid enough to
maintain the compressor frame level and the com-
pressor in alignment is required. The compressor
frame must be leveled and secured with foundation
bolts, and full uniform contact must be maintained
between the frame and foundation. No piping
loads shall be transmitted to the compressor at the
external connections.

4.2 VENTILATION AND COOLING

For air---cooled compressors, select a location to
permit sufficient unobstructed air flowing in and out
to the compressor to keep the operating tempera-
ture stable. The minimum distance that the com-
pressor should be from surrounding walls is three
(3) feet (1m). To prevent excessive ambient tem-
perature rise, it is imperative to provide adequate
ventilation.
For water---cooled compressors, it is necessary to
check the cooling water supply. The water system
must be capable of supplying the flows shown in
Table I ---Water Supply Requirements (Water---
cooled), and must be maintained at all times.
These figures apply to a compressor running at full
load with an aftercooler. For cooler water or a par-
tially loaded compressor, slightly less water is re-
quired. However, for hotter water the flow require-
ments are significantly greater.
Table 2---Ventilation Requirements indicates the
ventilation requirements necessary to keep the
compressor running at a normal operating temper-
TABLE 1-- WATER SUPPLY REQUIREMENTS (WATER-- COOLED)
WATER TEMP .
0˚F (˚C)
70 (21)
80 (26.6)
(I) Water pressure should be between 25 and 75 psig (1.7 and 5.2 bar).
TABLE 2-- VENTILATION REQUIREMENTS (I)
Cooling Type
Motor HP/KW
Fan Air CFM
3
M
/Hr (II)
Ventilating Air/
Heat Rejection
BTU/Hour
KCal/Hour
Cooling Water/
Heat Rejection
BTU/Hour
Kcal/Hour
(I) Values based on: 100% RH, 85˚F Ambient
(II) Applies to compressor with canopy only (vent fan).
25HP (18KW)
3.75 (14.2)
5.00 (18.9)
Air ---cooled with Aftercooler
25/18
30/22
2500/4250
2500/4250
76980/
88800/
19500
22500
ature. The fan air requirement is the volume of air
which must flow through the compressor for proper
ventilation. The specified heat rejection require-
ment is the amount of heat that is radiated by the
compressor. This heat must be removed to assure
a normal operating temperature. With air---cooled
compressors it is possible to use this heat for space
heating, providing no additional pressure drop is
created across the fan. Consult a Sullair office for
assistance in utilizing this heat.
DO NOT install a water---cooled or an air---cooled/
aftercooled compressor where it will be exposed to
temperatures less than 32_F(0_C).

4.3 SERVICE AIR PIPING

Service air piping should be installed as shown in
Figure 4---1. A shut---off valve should be installed to
isolate the compressor from the service line if re-
quired. Also notice that the service line should be
equipped with water legs and condensate drains
throughout the system.
"The Plastic Pipe Institute recommends against the
use of thermoplastic pipe to transport compressed
air or other compressed gases in exposed above
ground locations, e.g. in exposed plant piping." (I)
Sullube 32 should not be used with PVC piping sys-
tems. It may affect the bond at cemented joints. Cer-
tain other plastic materials may also be affected.
(I) Plastic Pipe Institute, Recommendation B,
Adopted January 19, 1972.
WATER FLOW (I)
GMP (LITERS)
30HP (22KW)
4.50 (17.0)
6.00 (22.7)
40/30
25/18
3500/5950
720/1220
118320/
8500/
29900
2150
Section 4

INSTALLATION

WARNING
!
40HP (30KW)
5.75 (21.8)
7.50 (28.4)
Water ---cooled
30/22
30/40
720/1220
720/1220
10000/
13000
2550
3300
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ls-10 30hpLs-10 18kwLs-10 22kwLs-10 30kwLs-10 40hpLs-10 30hp 24kt ... Show all

Table of Contents