8.8
Setback Operation
(1) Press and hold "Menu" and "Back/Help"on the wired controller simultaneously for at least three seconds
during the normal mode (unit stoppage).
The Test Run menu will be displayed.
(2) Select "Input/Output" from the Test Run menu and press "OK".
(3) Select either "Input 1" or "Input 2" and change the setting to "09".
(4) Build a circuit such as shown below.
No Voltage "a" Contact
When the card key is inserted (i.e.
someone is in the room), then the
contact turns ON.
(5) Temperature compensation for the setback function can be selected on the wired controller.
Refer to "Function Selection by Wired Controller" section for details.