(6) Refrigerant Cycle No. Setting (RSW2 and DSW5)
This setting is required. The unit arrives with all
settings in the OFF position.
(7) Fuse Recover (DSW7)
* Factory Setting
* In the case of applying high voltage to the terminal 1 and 2 of TB2,
the 0.5A fuse on the PCB is cut. In such a case, first reconnect the
wirings correctly to TB2, and then set the No.1 pin to ON.
(8) Optional (DSW8)
No setting is required. This is for setting the model code of the indoor unit.
NOTES:
● The "■" mark indicates setting for DIP switches. Figures show setting before shipment.
● When the unit number and the refrigerant cycle are set, record the unit number and refrigerant cycle to
facilitate service and maintenance thereafter.
Turn OFF all power supply of the indoor units and the outdoor units before DIP switch settings.
Otherwise, the setting will be invalidated and not take effect.
8.6

Selecting Static Pressure with Electrical Wiring Connection

Change the fan motor connection depending on the required static pressure according to the table as follows:
Model
Voltage
208V
(H,Y)IDH072B21S
230V
208V
(H,Y)IDH096B21S
230V
*: Factory Setting
P01432Q-rev.1
ON
1
2
OFF
NOTICE
Static Pressure
0.28 in.W.G. (70 Pa)
0.88 in.W.G. (220 Pa) *
0.64 in.W.G. (160 Pa)
1.16 in.W.G. (290 Pa) *
0.32 in.W.G. (80 Pa)
0.88 in.W.G. (220 Pa) *
0.70 in.W.G. (175 Pa)
1.18 in.W.G. (295 Pa) *
Refrigerant Cycle No. Setting
DSW5 (Tens Digit)
RSW2 (Units Digit)
Setting
Position
ON
OFF
1 2 3 4 5 6
Before shipment, DSW5 and RSW2 are set at "0".
For the units supporting H-LINK II,
the ref. cycle No. can be set for Max. 64 cycles.
(No. 0~63)
Printed
STD ESP
HIGH ESP
STD ESP
HIGH ESP
STD ESP
HIGH ESP
STD ESP
HIGH ESP
Ex.) Set at No.5 Cycle
DSW5
Set by inserting
slotted screwdriver
into the groove.
0
1 2 3 4 5 6
Set All Pins OFF
RSW2
0
Set at "5"
ON
1
2
OFF
ON
1 2 3
OFF
Printed "STD ESP"
Power Line
STD ESP
Connector
Printed "HIGH ESP"
Power Line
HIGH ESP
Connector
ON
OFF
31