York IDH072B21S Series Installation And Maintenance Manual page 29

Inverter-driven multi-split system heat pump air conditioners, ducted high static
Table of Contents

Advertisement

(1) Connect the cable for the optional controller or the optional extension cable to the terminals inside the
electrical box through the connecting hole of the cabinet.
(2) Connect the power supply and the ground wiring to the terminals in the electrical box.
(3) Connect the cables between the indoor unit and the outdoor unit to the terminals inside the electrical box.
(4) Connect cables to their corresponding terminal number and the similarly marked band.
(5) Connect the communication cable between those indoor units connected to the same outdoor unit.
(6) Do not connect the main power supply wiring to the communication line (Terminals A, B, 1 and 2 of
TB2). If connected, the printed circuit board (PCB) will be destroyed.
(7) Tightly clamp the power supply wiring and communication cables using the cable band inside the
electrical box.
NOTE:
When the standard wire is used for the field-wiring
connection, the M4 crimping terminal should be used.
When the single wire is used, fashion it into the shape
as shown at right and connect it in order to tighten
the washer uniformly. The screws at the terminal
block should be tightened according to the torque
specification as shown in the table above.
(8) All electrical work should be performed in strict accordance with electrical schematics in the "Installation
and Maintenance Manual".
(9) If Power Supply Voltage (208V/230V) is introduced into the Communication Line:
If 208V/230V are applied to the communication line at (Terminals 1 and 2 of TB2) by mistake, the fuse
on the PCB for the communication line will blow. In this case, perform the recovery work as shown in
the diagrams below.
(a) Reconnect the wirings correctly.
(b) Set the No.1 pin at DSW7 (on the PCB) to ON.
Upon PCB recovery after the fuse has been replaced, if 208V / 230V is reintroduced into the
communication line, the PCB will be seriously damaged and will not recover.
R
AC 208V/230V
5V
P01432Q-rev.1
S
A
B
1
2
L1
L2
Incorrect Wiring
Connect it with
Crimping Terminal.
R
S
A
L1
L2
AC 208V/230V
5V
Reconnect wirings correctly.
Connect it Direct
As Shown Below.
Stranded Wire
Single Wire
PCB
B
1
2
DSW7
ON
OFF
1 2
Set No.1 Pin
at ON side.