York Predator ZR series Installaton Manual

York Predator ZR series Installaton Manual

W/smart equipment. 3 - 5 ton 60 hertz
Table of Contents

Advertisement

R-410A
ZR SERIES W/SMART EQUIPMENT™
3 - 5 Ton
60 Hertz
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Preceding Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Side Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Power And Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Optional Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Optional Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Options/Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Economizer Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Dry Bulb Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Single Enthalpy Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Dual Enthalpy Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Auto . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1 ZR037-061 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 ZR037-061 Unit Accessory Weights . . . . . . . . . . . . . . . . . . . . 8
4 ZR037-061 Unit Physical Dimensions . . . . . . . . . . . . . . . . . . 11
5 ZR037-061 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Side Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7 Left/End Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8 Control Wire Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10 Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11 Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . . 27
12 Gas Pipe Sizing - Capacity of Pipe . . . . . . . . . . . . . . . . . . . . 28
13 Gas Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . . . . 29
15 Supply Air Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
16 Altitude/Temperature Correction Factors . . . . . . . . . . . . . . . 38
17 ZR037-061 Side Duct Application . . . . . . . . . . . . . . . . . . . . . 40
1 Unit Shipping Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Condenser Covering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Compressor Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
®
4 Predator
Component Location (ZR037 Shown) . . . . . . . . . . 6
5 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Unit 6 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7 Center of Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
8 ZR037 Physical Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9 ZR049-061 Physical Dimensions . . . . . . . . . . . . . . . . . . . . . 10
10 ZR037-061 Unit Bottom Duct Openings . . . . . . . . . . . . . . . . 12
11 ZR037-061 Unit Electrical Entry . . . . . . . . . . . . . . . . . . . . . . 13
12 ZR037-061 Unit Side Duct Openings . . . . . . . . . . . . . . . . . . 13
13 ZR037-061 Unit Left/End Duct Opening . . . . . . . . . . . . . . . . 14
14 ZR037-061 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
15 ZR037-061 Transition Roof Curb . . . . . . . . . . . . . . . . . . . . . 15
16 Side Duct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

TABLE OF CONTENTS

Free Cooling Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Power Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Airflow Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Air Balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Checking Air Quantity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Cooling Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . 46
Cooling Operation Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Reheat Mode Sequence Of Operation . . . . . . . . . . . . . . . . . . 48
Electric Heating Sequence Of Operations. . . . . . . . . . . . . . . . 49
Electric Heat Operation Errors . . . . . . . . . . . . . . . . . . . . . . . 49
Gas Heating Sequence Of Operations . . . . . . . . . . . . . . . . . . 50
Gas Heating Operation Errors . . . . . . . . . . . . . . . . . . . . . . . 50
Start-Up (Cooling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Start-Up (Gas Heat) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Checking Gas Heat Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Charging The Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Control Board Navigation Components . . . . . . . . . . . . . . . . . . . . 55
Start-Up Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
LIST OF TABLES
18 ZR037-061 Bottom Duct Application. . . . . . . . . . . . . . . . . . . 41
19 RPM Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
20 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 42
21 Power Exhaust Specifications . . . . . . . . . . . . . . . . . . . . . . . . 42
22 Motor Sheave Datum Diameters . . . . . . . . . . . . . . . . . . . . . . 44
23 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . . . . 45
24 Electric Heat Limit Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
25 Electric Heat Anticipator Setpoints . . . . . . . . . . . . . . . . . . . . 49
26 Gas Heat Anticipator Setpoints . . . . . . . . . . . . . . . . . . . . . . . 51
27 Gas Rate Cubic Feet Per Hour . . . . . . . . . . . . . . . . . . . . . . . 53
28 Gas Heat Stages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
29 Smart Equipment™ UCB Details . . . . . . . . . . . . . . . . . . . . . 56
32 ZR037 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
33 ZR049 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
34 ZR061 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
LIST OF FIGURES
20 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
21 Field Wiring Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
22 Typical Low Voltage Field Wiring . . . . . . . . . . . . . . . . . . . . . 19
23 Side Entry Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
24 Bottom Entry Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
25 SE-ECO1001-0 Economizer Controller . . . . . . . . . . . . . . . . 33
26 Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
27 Altitude/Temperature Correction Factors . . . . . . . . . . . . . . . 38
28 Dry Coil Delta P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
29 Reheat Operation Piping Schematic . . . . . . . . . . . . . . . . . . 48
30 Cooling Operation Piping Schematic . . . . . . . . . . . . . . . . . . 48
31 Typical Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
32 Typical Two Stage Gas Valve . . . . . . . . . . . . . . . . . . . . . . . 55
33 Typical Single Stage Gas Valve . . . . . . . . . . . . . . . . . . . . . . 55
34 Unit Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Advertisement

Table of Contents
loading

Summary of Contents for York Predator ZR series

  • Page 1: Table Of Contents

    R-410A ZR SERIES W/SMART EQUIPMENT™ 3 - 5 Ton 60 Hertz TABLE OF CONTENTS General ..........2 Free Cooling Operation .
  • Page 2: General

    5167540-YIM-H-0518 General ® ® York Predator units are single package air conditioners with optional gas heating designed for outdoor installation on a Before performing service or maintenance operations on rooftop or slab and for non-residential use. These units can be unit, turn off main power switch to unit.
  • Page 3 Inspection Renewal Parts ® As soon as a unit is received, it should be inspected for possible Contact your local York parts distribution center for authorized damage during transit. If damage is evident, the extent of the replacement parts. damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in...
  • Page 4 5167540-YIM-H-0518 Nomenclature ® 3-5 Ton ZR York Model Number Nomenclature Z R 037 C A 2 A 1 Product Generation Product Category 1 = First Generation Z = A/C, Single Pkg., R-410A Cabinet Options A = Std Cabinet Product Identifier...
  • Page 5: Installation

    5167540-YIM-H-0518 Remove the condenser coil external protective covering Installation prior to operation. Installation Safety Information Remove the toolless doorknobs and instruction packet prior to installation. Read these instructions before continuing this appliance installation. This is an outdoor combination heating and cooling unit.
  • Page 6: Limitations

    Roof curbs for transitioning (stainless steel option) from York Sunline™ footprint to the ZH Series footprint One or Two stage gas heating to are available Side entry power maintain warm, comfortable...
  • Page 7: Location

    If a unit is to be installed on a roof curb other than a personal injury. Typical contaminates include: ® York roof curb, gasketing must be applied to all permanent wave solution, chlorinated waxes and surfaces that come in contact with the unit underside.
  • Page 8: Weights And Dimensions

    5167540-YIM-H-0518 All panels must be secured in place when the unit is lifted. The condenser coils should be protected from rigging cable damage with plywood or other suitable material. FRONT LEFT Figure 6: Unit 6 Point Load Weight FRONT LEFT FRONT LEFT Figure 5: Unit 4 Point Load Weight...
  • Page 9: Zr037 Physical Dimensions

    5167540-YIM-H-0518 29.75 15.51 29.52 59.00 Ø 25.31 See detail A for gas inlet 11 3/8 See detail B for drain location LEFT 4 3/16 FRONT 21 3/16 27 5/16 Figure 8: ZR037 Physical Dimensions Johnson Controls Ducted Systems...
  • Page 10: Zr049-061 Physical Dimensions

    5167540-YIM-H-0518 29.69 15.25 15.38 59.00 15.38 Ø 24.47 TYP. 2 PL. See detail A for gas inlet 11 3/8 See detail B for drain location LEFT 4 3/16 FRONT 21 3/16 27 5/16 Figure 9: ZR049-061 Physical Dimensions Johnson Controls Ducted Systems...
  • Page 11: Zr037-061 Unit Physical Dimensions

    5167540-YIM-H-0518 Table 4: ZR037-061 Unit Physical Dimensions Dimension (in.) Unit Model Number ZR037 22 1/8 18 3/16 15 3/16 6 3/16 ZR049 22 1/8 18 3/16 15 3/16 6 3/16 ZR061 22 1/8 18 3/16 15 3/16 6 3/16 Detail A Detail B 3.184 Gas Pipe Inlet...
  • Page 12: Zr037-061 Unit Bottom Duct Openings

    5167540-YIM-H-0518 TOP VIEW 32 11/16 6 13/16 6 13/16 RETURN SUPPLY 27 1/2 LEFT RIGHT 20 1/8 19 1/8 17 1/8 12 5/16 Bottom condensate drain 14 1/2 25 9/16 Bottom gas supply entry 16 3/8 18 1/16 FRONT Bottom power, control and convenience outlet wiring entry 3X Ø...
  • Page 13: Side Duct Dimensions

    5167540-YIM-H-0518 Disconnect Swith Cover Power Entry Ø 2-1/2 Control Entry Ø 7/8 Power Entry Ø 2-1/2 Convenience Outlet Cover Convenience Outlet Power Entry Ø 7/8 FRONT Figure 11: ZR037-061 Unit Electrical Entry 1 8 - 1 /4 D o t P l u g s Return Supply Air 2 - 3 1 /3 2...
  • Page 14: Left/End Duct Dimensions

    5167540-YIM-H-0518 4-5/16 Figure 13: ZR037-061 Unit Left/End Duct Opening Table 7: Left/End Duct Dimensions Dimension (in.) Unit Model Number ZR037 30.357 13.365 22.516 ZR049 30.357 13.365 22.516 ZR061 30.357 13.365 22.516 RIGHT 80-5/8 INSULATED DECK UNDER CONDENSER SECTION SUPPLY RETURN 2 TYP.
  • Page 15: Ductwork

    5167540-YIM-H-0518 2 TYP 23 4 30-1/2 50-1/2 80-5/8 RETURN SUPPLY 76-5/8 59-1/4 FRONT RIGHT 64-1/4 Figure 15: ZR037-061 Transition Roof Curb in place from the factory) and two screws. It’s a snug fit for the Ductwork panel when sliding it between the heat exchanger and unit Ductwork should be designed and sized according to the bottom, but there is room.
  • Page 16: Side Panels

    5167540-YIM-H-0518 Condensate Drain The side condensate drain is reversible and maybe re-oriented to the rear of the cabinet to facilitate condensate piping. A condensate drain connection is available through the base pan for piping inside the roof curb. Trap the connection per Figure 20. The trap and drain lines should be protected from freezing.
  • Page 17: Filters

    5167540-YIM-H-0518 Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1. Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more.
  • Page 18: Field Wiring Disconnect

    5167540-YIM-H-0518 Power Wiring Detail Units are factory wired for the voltage shown on the unit Power wiring is brought into the unit through the side of the unit nameplate. Refer to Electrical Data Table 9 to size power or the basepan inside the curb. wiring, fuses, and disconnect switch.
  • Page 19: Control Wire Sizes

    5167540-YIM-H-0518 thermostat to the unit. Refer to Table 8 for control wire sizing Thermostat Wiring and maximum length. A two stage thermostat must be used and should be located on an inside wall approximately 56 inch above the floor where it will Table 8: Control Wire Sizes not be subject to drafts, sun exposure or heat from electrical fixtures or appliances.
  • Page 20: Electrical Data

    5167540-YIM-H-0518 Table 9: Electrical Data ZR037-061 Standard Indoor Blower - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size...
  • Page 21 5167540-YIM-H-0518 ZR037-061 Hi Static Indoor Blower - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh RLA LRA Model...
  • Page 22 5167540-YIM-H-0518 ZR037-061 Standard Indoor Blower - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh RLA LRA Model Stages...
  • Page 23 5167540-YIM-H-0518 ZR037-061 Hi Static Indoor Blower - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh RLA LRA Model...
  • Page 24: Physical Data

    5167540-YIM-H-0518 Table 10: Physical Data ZR037-061 Single Stage Gas Heat Physical Data Models Component ZR037 ZR049 ZR061 Nominal Tonnage AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (Btu) 36500 49000 62000 AHRI net capacity (Btu) 35500 46900 58000 12.2 12.1 12.1 SEER...
  • Page 25 5167540-YIM-H-0518 ZR037-061 Single Stage Gas Heat Physical Data (Continued) Models Component ZR037 ZR049 ZR061 Nominal Tonnage CONDENSER FAN DATA Quantity of fans Fan diameter (Inch) Type Prop Prop Prop Drive type Direct Direct Direct Quantity of motors Motor HP each No.
  • Page 26 5167540-YIM-H-0518 ZR037-061 Two Stage Gas Heat Physical Data Models Component ZR037 ZR049 ZR061 Nominal Tonnage AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (Btu) 36500 49000 62000 AHRI net capacity (Btu) 35600 47000 58000 12.2 12.1 12.1 SEER 14.7 14.5 14.25 1200...
  • Page 27: Optional Electric Heat

    5167540-YIM-H-0518 ZR037-061 Two Stage Gas Heat Physical Data (Continued) Models Component ZR037 ZR049 ZR061 Nominal Tonnage CONDENSER FAN DATA Quantity of fans Fan diameter (Inch) Type Prop Prop Prop Drive type Direct Direct Direct Quantity of motors Motor HP each No.
  • Page 28: Optional Gas Heat

    5167540-YIM-H-0518 Optional Gas Heat These gas-fired heaters have aluminized-steel or optional stainless steel, tubular heat exchangers with spark ignition. OPTIONAL Gas Piping COIL GUARD Proper sizing of gas piping depends on the cubic feet per hour SHOWN of gas flow required, specific gravity of the gas and the length of run.
  • Page 29: Gas Heat Minimum Supply Air

    5167540-YIM-H-0518 Table 13: Gas Heat Minimum Supply Air Supply Air (CFM) Size Model Heat Size Heating (Tons) H06 / N06 2220 H08 / N08 2370 H12 / N12 1130 1800 H06 / N06 2220 H08 / N08 2370 H12 / N12 1290 2250 H08 / N08...
  • Page 30: Options/Accessories

    5167540-YIM-H-0518 For satisfactory operation, LP gas pressure must be 10.5 inch electric heaters have either fuses or circut breaker and are W.C. at the unit under full load. Maintaining proper gas intended for use with single point power supply. pressure depends on three main factors: Smoke Detectors The vaporization rate which depends on the temperature of the liquid and the “wetted surface”...
  • Page 31: Economizer Sequences

    5167540-YIM-H-0518 Economizer Dry Bulb Changeover The Economizer can be a factory installed option or a field For dry bulb economizer operation, the outside air is suitable for installed accessory. If factory installed, refer to the instructions free cooling if the outside air temperature is 1°F below the included with the outdoor air hood to complete the assembly.
  • Page 32: Power Exhaust

    5167540-YIM-H-0518 If the supply air temperature cannot be maintained within 5°F of compressor outputs will be de-energized as long as their the economizer setpoint, the first stage compressor (C1) will be minimum run timers have expired. turned on. Second stage compressor (C2) will be added as needed to keep the supply air temperature within the 5°F of the Power Exhaust economizer setpoint.
  • Page 33: Smart Equipment™ Economizer Board Details

    5167540-YIM-H-0518 Figure 25: SE-ECO1001-0 Economizer Controller Table 14: Smart Equipment™ Economizer Board Details Board Cover Description Function & Comments Label Label Directional orientation: viewed with the center text of the cover label upright ANALOG INPUTS Terminal at left on upper edge of economizer board 24 VAC common/0-10 VDC negative for Connects through circuit trace to 24V~ IN pin COM economizer actuator position feedback...
  • Page 34 5167540-YIM-H-0518 Table 14: Smart Equipment™ Economizer Board Details (Continued) Board Cover Description Function & Comments Label Label EconCtrlr parameter reports UCB-to-economizer board SA BUS communication status. Positive of the VDC (typically, a fluctuating 1.5 to 3.5 volts reading to C; at least 0.25 volts lower –...
  • Page 35 5167540-YIM-H-0518 Table 14: Smart Equipment™ Economizer Board Details (Continued) Board Cover Description Function & Comments Label Label 24 VAC hot connection to power the economizer board. 24 VAC transformer HOT Connects through circuit traces to R/24V~ terminals and pins distributed on the economizer board. ANALOG INPUTS Terminal on lower edge of economizer board 24 VAC hot supplied for the outdoor air 24V~...
  • Page 36: Supply Air Limitations

    5167540-YIM-H-0518 Table 14: Smart Equipment™ Economizer Board Details (Continued) Board Cover Description Function & Comments Label Label 24 VAC common/0-5 VDC negative for the Connects through circuit trace to 24V~ IN pin COM building pressure sensor BINARY INPUTS at right on lower edge of economizer board Purge parameter reports input status (False with 0 VAC input- True with 24 VAC input).
  • Page 37 5167540-YIM-H-0518 Altitude and Temperature Correction for CFM, Static Pressure and Power. The information below should be used to assist in application of Procedure for adjusting belt tension: product when being applied at altitudes at or exceeding 1000 feet above sea level. 1.
  • Page 38: Altitude/Temperature Correction Factors

    5167540-YIM-H-0518 Table 16: Altitude/Temperature Correction Factors Altitude (Ft.) Temp. 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 1.019 0.982...
  • Page 39 5167540-YIM-H-0518 Drive Selection Determine side or bottom supply duct Application. Determine desired airflow. Calculate or measure the amount of external static pressure. • Add or deduct any additional static resistance from “Additional Static Resistance Table”. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table.
  • Page 40: Zr037-061 Side Duct Application

    5167540-YIM-H-0518 Airflow Performance Table 17: ZR037-061 Side Duct Application ZR037 (3.0 Ton) Side Duct Available External Static Pressure - IWG Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP &...
  • Page 41: Zr037-061 Bottom Duct Application

    5167540-YIM-H-0518 Table 18: ZR037-061 Bottom Duct Application ZR037 (3.0 Ton) Bottom Duct Available External Static Pressure - IWG Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP &...
  • Page 42: Air Balance

    5167540-YIM-H-0518 Table 19: RPM Selection Size Airflow Motor Blower 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully Model (Tons) Option Sheave Sheave Open Open Open Open Open Open Closed 1VP34 AK61 Std. (3.0) 1VL44 AK59 1004 1066 1129...
  • Page 43: Dry Coil Delta P

    5167540-YIM-H-0518 Select the correct blower performance table for the unit from Tables 16 and 18. Tables are presented for side and downflow configuration. Determine the unit Measured CFM from the Blower Failure to properly adjust the total system air quantity Performance Table, External Static Pressure and the can result in extensive blower damage.
  • Page 44: Motor Sheave Datum Diameters

    5167540-YIM-H-0518 EXAMPLE Supply Air Drive Adjustment A 4 ton unit was selected to deliver 1,700 CFM with a 1.5 HP motor, but the unit is delivering 1,400 CFM. The variable pitch motor sheave is set at 3 turns open. Before making any blower speed changes review the Use the equation to determine the required DD for the new installation for any installation errors, leaks or undesirable motor sheave,...
  • Page 45: Additional Static Resistance

    5167540-YIM-H-0518 Table 23: Additional Static Resistance Electric Heat kW Size Model CFM Cooling Only Economizer 4” Pleated Filter (Tons) 0.05 -0.05 0.01 0.00 0.00 0.00 0.01 0.01 0.01 1000 0.05 -0.03 0.02 0.00 0.00 0.00 0.02 0.02 0.02 1100 0.04 -0.02 0.03 0.01...
  • Page 46: Operation

    5167540-YIM-H-0518 If the outdoor air enthalpy is above the setpoint, “Y1” energizes Operation the compressor and condenser fan motor only. Cooling Sequence Of Operation When there is a call for “Y2”, the low voltage control circut from “R” to “Y2 is completed. The UCB energizes the compressor. If ®...
  • Page 47 5167540-YIM-H-0518 throughout the cycle. The 5-minute off period is necessary to High-Pressure Limit Switch defrost the indoor coil. During cooling operation, if a high-pressure limit switch opens, Low ambient mode always begins with compressor operation. the UCB will de-energize the compressor, initiate the ASCD Compressor minimum run time may extend the minutes of (Anti-short cycle delay).
  • Page 48: Reheat Mode Sequence Of Operation

    5167540-YIM-H-0518 refrigerant flow in the evaporator reheat coil and condenser coil Reheat Mode Sequence Of Operation #1. See Figure 29. The MagnaDRY reheat mode of operation is designed to When there is a call for the first stage of cooling while there is remove latent heat (Humidity) from a space when there are low still a call for dehumidification, no operational change is made.
  • Page 49: Electric Heating Sequence Of Operations

    5167540-YIM-H-0518 Electric Heating Sequence Of Operations Table 24: Electric Heat Limit Setting The following sequence describes the operation of the electric LIMIT heat section. HEATER UNIT (TONS) VOLTAGE SWITCH OPENS °F Single stage heating: a. Upon a call for heating by the thermostat, the heater ZR037 (3) 208/230 relay (RA) will be energized.
  • Page 50: Gas Heating Sequence Of Operations

    5167540-YIM-H-0518 Gas Heating Sequence Of Operations Recycle Operation When a flame is lost after the flame stabilization period, a recy- Single stage heating: cle operation occurs. If the unit fails after five recycle attempts, When the thermostat calls for the first stage of heating, the low- the furnace is locked-out for one hour.
  • Page 51: Start-Up (Cooling)

    5167540-YIM-H-0518 voltage is no longer sensed at the GV, the UCB will de-energize Roll-out Switch (ROS) the indoor blower following the elapse of the fan off delay for The roll-out switch is wired in series with the pressure switch. heating. As such, the ICB cannot distinguish the roll-out switch operation If voltage has been sensed at the GV for at least 15 seconds from that of the pressure switch.
  • Page 52: Start-Up (Gas Heat)

    5167540-YIM-H-0518 Check blower drive belt tension. Post Start Checklist Check the unit supply air (CFM). After the entire control circuit has been energized and the heating section is operating, make the following checks: Measure evaporator fan motor's amp draw. Check for gas leaks in the unit piping as well as the supply Set the room thermostat fan switch to off.
  • Page 53: Gas Rate Cubic Feet Per Hour

    5167540-YIM-H-0518 If necessary, adjust the regulator as discussed in the Table 27: Gas Rate Cubic Feet Per Hour section "Manifold Gas Pressure Adjustment". Repeat Size of Test Dial Seconds for Steps 1-5. One Rev. 1/2 cu. ft. 1 cu. ft. Two Stage Gas Heat This unit has two stages of gas heat.
  • Page 54: Gas Heat Stages

    5167540-YIM-H-0518 Turn on power to the unit. Table 28: Gas Heat Stages Set thermostat to call for heat and start furnace. Unit 2nd Stage Total # of Burner 1st Stage If necessary, using a screwdriver, turn the adjustment Input Input Tubes Input (Mbh) Size...
  • Page 55: Charging The Unit

    5167540-YIM-H-0518 Remove the heat shield on top of the manifold supports. ELECTRICAL Burners are now accessible for inspection and/or ADJUSTMENT TERMINALS replacement. NOTE: Reverse the above procedure to replace the assemblies. Make sure that burners are level and seat at the rear of the gas INLET OUTLET PRESSURE...
  • Page 56: Smart Equipment™ Ucb Details

    5167540-YIM-H-0518 THERMOSTAT WIRED HERE SD-24 Figure 34: Unit Control Board Table 29: Smart Equipment™ UCB Details Description Function & Comments Terminal Directional orientation: viewed with silkscreen labels upright Limit, 24 VAC power and shutdown connections from unit wiring harness at left on upper edge of UCB Monitored 24 VAC input through heat section limit If voltage is absent, indicating the heat section is over- LIMIT...
  • Page 57: Yim-H

    5167540-YIM-H-0518 Table 29: Smart Equipment™ UCB Details (Continued) Description Function & Comments Terminal Thermostat connection strip on left edge of UCB 1st stage heating request, 24 VAC input switched Not effective for cooling-only units from R 2nd stage heating request, 24 VAC input switched Not effective for cooling-only units or units with single-stage from R heat sections...
  • Page 58 5167540-YIM-H-0518 Table 29: Smart Equipment™ UCB Details (Continued) Description Function & Comments Input required for operation; 3.625 VDC reading RAT+ to RAT– Return Air Temperature sensor input from 10KΩ with open circuit. Used in return air enthalpy calculation. RAT+ @ 77°F, Type III negative temperature coefficient Substitutes for space temperature if no other space thermistor temperature input is present.
  • Page 59 5167540-YIM-H-0518 Table 29: Smart Equipment™ UCB Details (Continued) Description Function & Comments Terminal at lower right corner of UCB Output relay circuitry is isolated from other UCB components 24 VAC hot for H1, H2, CN-FAN, AUX HGR, FAN 24V FOR OUTPUTS and the 24 VAC hot source may be from a second transformer C1 and C2 output relay contact switching in the unit...
  • Page 60 5167540-YIM-H-0518 Table 29: Smart Equipment™ UCB Details (Continued) Description Function & Comments Not effective for one stage compressor UCBs. Input is only considered if C2 output is needed; input must be present to 24 VAC hot return from refrigerant circuit 2 High allow C1 output.
  • Page 61: Cable For Fc Buses And Sa Buses In Order Of Preference

    5167540-YIM-H-0518 Table 29: Smart Equipment™ UCB Details (Continued) Description Function & Comments Factory wired SA Bus connector Optional communication sub-board at center of UCB Terminal FC BUS connections on left edge of the communication board Positive of the VDC (typically, a fluctuating 1.5 to 3.5 volts FC (“Field Connected”) BUS BACnet MSTP reading to COM;...
  • Page 62: Cable For Fc Buses And Sa Buses In Order Of Preference . 61 31 Flash Codes For The Gas Heat Ignition Control Board

    5167540-YIM-H-0518 Table 31: Flash Codes for the Gas Heat Ignition Control Board Flash Description Technician Corrective Action Code Normal Operation - no status or error information Heartbeat currently needs to be displayed Verify line voltage is present at the primary of the 75VA transformer, verify No Power to Control - 24v AC is not present to the 24v AC is present at the secondary of the 75VA transformer.
  • Page 63: Zr037 Charging Table

    5167540-YIM-H-0518 Table 32: ZR037 Charging Table Air Flow Outdoor Suction Suction Liquid Liquid Delta T Compr. Indoor Db/Wb Pressure Temp. Pressure Temp. amps 300 Cfm/Ton 80/62 300 Cfm/Ton 80/67 300 Cfm/Ton 80/72 300 Cfm/Ton 75/63 400 Cfm/Ton 80/62 400 Cfm/Ton 80/67 400 Cfm/Ton 80/72...
  • Page 64: Zr061 Charging Table

    5167540-YIM-H-0518 Table 34: ZR061 Charging Table Air Flow Outdoor Suction Suction Liquid Liquid Delta T Compr. Indoor Db/Wb Pressure Temp. Pressure Temp. amps 300 Cfm/Ton 10.2 80/62 11.2 300 Cfm/Ton 10.4 80/67 11.4 300 Cfm/Ton 10.3 80/72 11.5 300 Cfm/Ton 10.1 75/63 11.2...
  • Page 65: Start-Up Sheet

    5167540-YIM-H-0518 Start-Up Sheet Johnson Controls Ducted Systems...
  • Page 66 5167540-YIM-H-0518 Johnson Controls Ducted Systems...
  • Page 67 5167540-YIM-H-0518 Johnson Controls Ducted Systems...
  • Page 68 5167540-YIM-H-0518 Johnson Controls Ducted Systems...
  • Page 69 5167540-YIM-H-0518 Johnson Controls Ducted Systems...
  • Page 70 Subject to change without notice. Printed in U.S.A. 5167540-YIM-H-0518 Copyright © 2018 by Johnson Controls, Inc. All rights reserved. Supersedes: 5167540-YIM-G-0717 York International Corporation 5005 York Drive Norman, OK 73069...