Pressure Switches - Viessmann Vitodens 200-W B2HA 112 Installation Instructions Manual

Wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 112:
Table of Contents

Advertisement

Start-up
Vitodens 200-W B2HA 112, 150, 399, 530 Service

Pressure Switches

Rear View
GDW1 low pressure gas switch (n.c.)
When the gas pressure rises above 4" w.c. the switch
will open and the burner will operate. When the gas
pressure drops below 4" w.c. the switch will close and
the boiler control will shut off the burner.
GDW2 high pressure gas switch (n.o.)
When the gas pressure rises above 3.5" w.c. the switch
will close and the boiler control will shut off the burner.
If either switch is activated (closed position) the burner
will shut down, but no fault will be displayed on the
control.
Check address 38 in coding 2, if the value is 2 then one
of the switches has been activated (closed).
21

Hide quick links:

Advertisement

Table of Contents
loading