Vitodens 200-W B2HA 112, 150, 399, 530 Installation
Wall Mounting
Boiler Stand
Fitting the wall mounting bracket
Following are the installation instructions for the mounting
bracket on each material. See the instructions applicable
to your installation requirements.
Installing the wall mounting bracket
The Vitodens 200-W B2HA can be wall-mounted on a
concrete wall.
Note: The enclosed screws and rawl plugs are only
suitable for concrete. For other construction
materials, use anchors and bolts that are suitable
for 330 lb (150 kg) loads.
Installation of mounting bracket on brick/concrete wall
1. Drill holes 7
/
in. (12 mm).
31
64
2. Install rawl plugs and screw mounting bracket
to wall.
3. Ensure the mounting bracket is level.
CAUTION
Whichever mounting method is used, ensure that the
bracket is tightly and securely fastened to wall. Failure
to secure boiler properly could cause boiler to loosen,
posing a severe safety hazard.
The boiler stand is used for free-standing installation of a
single boiler within the mechanical room.
When using the boiler stand, ensure that the stand is
securely fastened to the floor (recommended concrete
expansion anchors are Hilti model KB-TZ e x 4 or
equivalent.
Boiler Connections
15