Viessmann Vitodens 200-W B2HA 112 Installation Instructions Manual

Viessmann Vitodens 200-W B2HA 112 Installation Instructions Manual

Wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 112:
Table of Contents

Advertisement

VIESSMANN MANUFACTURING COMPANY (U.S.) INC. ("Viessmann")
STANDARD LIMITED WARRANTY
For Hydronic Heating Boilers - Gas-Fired Condensing Stainless
Steel Boilers Only (the "Standard Warranty" or the "Warranty")
TERMS AND CONDITIONS OF WARRANTY
Viessmann provides this Warranty only to the original end user
purchaser (the "Owner") of a Viessmann Stainless Steel Hydronic
Heating Boiler of less than 530,000 BTU output purchased after
September 1, 2016, in the United States of America for installations
in the United States (the "Boiler"), provided the Owner uses the Boiler
at the site of original installation in accordance with the terms hereof.
This Warranty provides specific legal rights. You may have other
rights which vary from State to State in the United States of
America. The rights in this Warranty are conditioned upon: (a) the
proper installation of the Boiler in accordance with all applicable
rules, regulations, industry standards and Viessmann instructions
by a mechanical contractor or installer whose principal occupation is
the sale and installation of heating, plumbing, and/or air conditioning
equipment and who is properly licensed under all relevant and/or
applicable laws of the jurisdiction in which the Boiler is installed
("Contractor"); (b) proper operation, and maintenance of the Boiler
by a Contractor in accordance with the product manuals; (c) the
original and continuous installation and use of the Boiler by an
Owner within the United States of America; and (d) performance of
warranted part replacements or repairs by a Contractor.
WARRANTY AND WARRANTY PERIODS
Viessmann's obligation under this Warranty is limited to the repair
or replacement, at the sole discretion of Viessmann, of any goods
or parts which do not conform to the express Warranty provided
herein. Labor and all other costs for the examination, removal
and/or re-installation of defective parts, and transportation costs
for defective or replacement parts, are not covered by this Warranty.
LIMITED TWO (2) YEAR WARRANTY
Viessmann warrants that the Boiler enclosure, burner, controls, and
other accessories Viessmann provides as standard equipment on
the Boiler will be free from defects in material and workmanship for
TWO (2) YEARS from the Date of Original Installation of the Boiler.
LIMITED FIVE (5) YEAR WARRANTY FOR RESIDENTIAL APPLICATIONS
If the Owner uses the Boiler exclusively for personal, family and
household purposes in a single family dwelling or a residential
building where Boiler
services
("Residential
Applications")
Boiler enclosure , burner, controls, and other accessories that
Viessmann provides as standard equipment on the Boiler will
be free from defects in material and workmanship for FIVE (5)
YEARS from the Date of Original Installation of the Boiler.
LIMITED TEN (10) YEAR WARRANTY FOR THE PRESSURE VESSEL
Viessmann warrants that the pressure vessel of the Boiler will be
free from defects in materials and workmanship resulting in a leak for
TEN (10) YEARS from the Date of Original Installation of the Boiler.
only the Owner's residence
Viessmann
warrants
that
LIMITED LIFETIME WARRANTY FOR THE PRESSURE VESSEL
AFTER THE TENTH (10TH) YEAR FOR RESIDENTIAL APPLICATIONS
If the Owner uses the Boiler exclusively in a Residential
Application, Viessmann warrants that the pressure vessel
will remain free from defects in materials and workmanship
resulting
in
a
leak
Repair or replacement of a pressure vessel defective in material or
workmanship after the tenth year in Residential Applications will
be made only upon the Owner's payment of a proportionate charge
based upon the length of time the pressure vessel has been installed.
The proportionate charge is the percentage of the then current
Viessmann list price of the pressure vessel when the warranty
claim is made, determined as follows: 11th year - Owner 20%,
Viessmann 80%; 12th year - Owner 40%, Viessmann 60%;
13th year - Owner 50%, Viessmann 50%; 14th year - Owner 60%,
Viessmann 40%; 15th year and beyond - Owner 75%, Viessmann 25%.
If a pressure vessel for the Boiler is no longer available when the
warranty claim is made, Viessmann will provide a new condensing
Boiler at the then current retail price subject to the following: The
Owner must pay the then current retail price for the replacement
boiler less a credit based upon (1) the percentage the list price
of the pressure vessel of the new boiler bears to the list price of
the entire boiler, and (2) Viessmann's share of the proportionate
charge detailed above. By way of example, if the pressure vessel
fails in the 14th year and the list price of the pressure vessel is
30% of the list price of the new boiler, the Owner will receive a
credit of 12% of the retail list price of the new boiler (30% of
Viessmann's 40% share of proportionate charge in the 14th year).
REPLACEMENT PARTS
Replacement or repaired parts provided under this Warranty are
warranted for the applicable unexpired period of this Warranty,
or the term of Viessmann's Parts Warranty, whichever is longer.
COMMENCEMENT OF WARRANTY PERIODS
The Warranty Periods commence on the date the Boiler is installed
(the "Date of Original Installation"). In the event of a dispute
as to the Date of Original Installation, the shipping date from
the
the Viessmann facility, as recorded in the books and records of
Viessmann, shall be deemed to be the Date of Original Installation.
during
the
life
time
of
5786 599 - 01 09/2016
the
boiler.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Vitodens 200-W B2HA 112 and is the answer not in the manual?

Questions and answers

Summary of Contents for Viessmann Vitodens 200-W B2HA 112

  • Page 1 Viessmann 80%; 12th year - Owner 40%, Viessmann 60%; applicable laws of the jurisdiction in which the Boiler is installed 13th year - Owner 50%, Viessmann 50%; 14th year - Owner 60%, (“Contractor”); (b) proper operation, and maintenance of the Boiler Viessmann 40%;...
  • Page 2 BY THREE (3) ARBITRATORS, ONE OF WHOM SHALL BE NOMINATED damages, so the above limitation or exclusion may not apply to you. BY VIESSMANN, ONE BY THE OWNER AND THE THIRD BY THE 2. THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER FIRST TWO NOMINEES IF THEY CAN AGREE AND OTHERWISE WARRANTIES.
  • Page 3 Installation Instructions for use by heating contractor Vitodens 200-W, B2HA Models 112, 150, 399, 530 Wall-mounted, gas-fired condensing boiler For operation with natural gas and liquid propane gas Heating input: 113 to 530 MBH 33 to 155 kW VITODENS 200-W Product may not be exactly as shown IMPORTANT Read and save these instructions...
  • Page 4: Product Documentation

    Safety Vitodens 200-W B2HA 112, 150, 399, 530 Installation Safety, Installation and Warranty Requirements Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life.
  • Page 5: About These Installation Instructions

    Safety Vitodens 200-W B2HA 112, 150, 399, 530 Installation Safety, Installation and Warranty Requirements (continued) Suppliers of fiberglass wool products recommend the Fiberglass wool and ceramic fiber materials following precautions be taken when handling these materials: WARNING - Avoid breathing fiberglass dust and contact with skin and eyes.
  • Page 6: Table Of Contents

    Table of Contents Vitodens 200-W B2HA 112, 150 Installation Page Safety Safety, Installation and Warranty Requirements.....2 Product documentation..........2 Warranty..............2 Licensed professional heating contractor....2 Contaminated air............2 Advice to owner............2 Carbon monoxide.............2 Fresh air..............2 Equipment venting...........2 About these Installation Instructions......3 General Information Important Regulatory and Installation Requirements..6...
  • Page 7 Table of Contents Vitodens 200-W B2HA 112, 150 Installation Page Boiler Connections (continued) Safety Connections...........30 Installing boiler safety devices.........30 Low water cut-off..........31 Waterside Flow............31 Waterside flow (primary circuit).......31 Installation Examples..........33 General..............33 Clearances............33 System Layout 1-10..........34 Alternative DHW Connection........44 Boiler in Heating/Cooling..........45 Boiler in heating/cooling application......45...
  • Page 8: General Information

    General Information Vitodens 200-W B2HA 112, 150, 399, 530 Installation Important Regulatory and Installation Requirements Codes The installation of this unit shall be in accordance with The following topics must be covered: local codes or, in the absence of local codes, use CAN/ Proper system operation sequence.
  • Page 9: For Installations On The Commonwealth Of Massachusetts

    VIESSMANN IS NOT RESPONSIBLE FOR ANY DAMAGES THAT THE FOLLOWING TEST PROCEDURE MAY RESULT IN BY OVERHEATING THE SYSTEM.
  • Page 10: Applicability

    General Information Vitodens 200-W B2HA 112, 150 Installation Applicability CAUTION The boiler serial number must be provided when ordering replacement parts. Some replacement parts are not reverse compatible with previous versions of the Vitodens 200-W B2HA boiler. IMPORTANT When ordering replacement parts, provide either the...
  • Page 11: Mechanical Room

    General Information Vitodens 200-W B2HA 112, 150, 399, 530 Installation Mechanical Room During the early stages of designing a new home, we recommend that proper consideration be given to constructing a separate mechanical room dedicated to the gas- or oil-fired heating equipment and domestic hot water storage tank(s).
  • Page 12: Set-Up

    Set-up Vitodens 200-W B2HA 112, 150, 399, 530 Installation Removing the Boiler Packaging Note: Visually inspect equipment packaging for damage. If damage is discovered, carefully remove the packaging and note any evidence of damage to the equipment. Save the shipping container for inspection by the carrier if damage has occurred.
  • Page 13: Prepare Boiler For Mounting

    Set-up Vitodens 200-W B2HA 112, 150, 399, 530 Installation Prepare Boiler for Mounting 1. Lift the boiler carefully to the upright position. Note: Before lifting the boiler to the upright position ensure the floor is level and clear of debris.
  • Page 14: Before Set-Up

    Set-up Vitodens 200-W B2HA 112, 150, 399, 530 Installation Before Set-up Before placing boiler in its installation location, ensure all CAUTION necessary accessories are installed. The boiler must be installed in such a way that gas ignition system components are protected from water (spraying, splashing, etc.) during boiler operation and...
  • Page 15: Boiler Connections

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Preparing the Connections Use an approved pipe sealant or teflon tape when connecting the following installation fittings. This section constitutes an overview only! Refer to subsequent sections for detailed information on individual piping connections.
  • Page 16 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Preparing the Connections (continued) This section constitutes an overview only! Refer to Note: When preparing gas, water and electrical subsequent sections for detailed information on individual connections in the field, see section entitled piping connections.
  • Page 17: Wall Mounting

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Wall Mounting Fitting the wall mounting bracket Following are the installation instructions for the mounting bracket on each material. See the instructions applicable to your installation requirements. Installing the wall mounting bracket The Vitodens 200-W B2HA can be wall-mounted on a concrete wall.
  • Page 18: Boiler Mounting

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Boiler Mounting Boiler mounting frame and bracket Install the boiler mounting frame to the wall studs and floor. Ensure the mounting bracket is level. To mount on wood or metal studs a cross bar or frame may be required as reinforcement.
  • Page 19 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Boiler Mounting (continued) Note: The connection box cover and the front encloser panel may have been already removed during unpacking. 1. Remove the external accessories connection box cover. 2. Loosen the screws at the bottom of the boiler (do not remove completely).
  • Page 20: Connections

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections Connecting power The Vitodens 200-W boiler has a external accessories connection box installed, which requires a 120VAC/12A power supply. Refer to the wiring diagram (see page 47). Boiler venting The Vitodens 200-W B2HA boiler comes with a pre-installed vent pipe adaptor.
  • Page 21: Gas Connection And Piping

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) Gas connection and piping 1. Refer to current CAN/CSA B149.1 and .2 or National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes for gas piping requirements and sizing.
  • Page 22 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) Legend Legend A Test firing valve A Shut off valve B Fuel pressure regulator/high gas pressure switch B Aux. low gas pressure switch C Low gas pressure switch...
  • Page 23: Gas Piping Pressure Test

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) Gas piping pressure test Heating water connections When performing the gas piping pressure test, ensure the 1. Thoroughly flush heating system (particularly before following requirements are met. connecting the boiler to an existing system).
  • Page 24: Dhw Storage Tank Information

    Viessmann DHW storage tank when mounting and securing DHW tank temperature sensor %. WARNING If a DHW storage tank other than a Viessmann Vitocell 100 or 300 tank is used, the installer must verify proper operation of the Viessmann DHW tank temperature sensor with original manufacturer of the tank.
  • Page 25: Accessing The Control Unit Connections

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) Accessing the control unit connections 1. Remove both screws from the external accessory connection box front plate and set aside. 2. Loosen both retaining screws as shown (do not remove).
  • Page 26 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) 5. Tilt the bottom of the external accessory connection box cover forward. 6. Pull the cover up to clear the locating pins and out to remove, then set aside.
  • Page 27: Routing The Connecting Cables

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) 12. Route all connecting cables to the appropriate areas and secure the cables to the control base using existing strain reliefs as shown. CAUTION When running and securing connecting cables on site, ensure that the maximum permissible temperatures of the cables are not exceeded.
  • Page 28: Connecting Dhw Sensor

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) Connecting DHW sensor 1. Attach the DHW sensor to the quick connect plugs provided from the boiler control board (see page 25). Install DHW tank temperature sensor as described in the Vitocell Installation Instructions supplied with the DHW storage tank.
  • Page 29: Control Base

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) Control base Note: See wiring diagram on page 47 for connection to the external accessory connection box. OUTDOOR TEMPERATURE TEMPERATURE SENSOR SENSOR...
  • Page 30: External Accessory Connection Box

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) External accessory connection box IMPORTANT Note: See wiring diagram on page 47 for connection to the control base. Electrical installations must comply with the latest edition of: In the U.S.A., the National Electrical Code (NEC), ANSI/NFPA 70 and any other state, local codes and/or regulations.
  • Page 31: Condensate Connection

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connections (continued) Condensate connection The Vitodens 200-W B2HA boiler comes with a built-in condensate trap. An external trap is not required when connecting the field drain to flexible discharge tubing.
  • Page 32: Safety Connections

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Safety Connections Installing boiler safety devices 1. Remove loosely pre-assembled combination pressure relief valve and drain valve assembly. 2. Apply sufficient amount of pipe sealant to both ends of all pipe fittings B,D,F,H and J and install onto coupling A and tees C and G.
  • Page 33: Low Water Cut-Off

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Safety Connections (continued) Low water cut-off A low water cut-off device may be required by local codes. If required, a low water cut-off device of an approved type (field supplied), is to be installed as per the manufacturers instructions.
  • Page 34 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Waterside flow (continued) Boiler B2HA 112, 399 maximum flow rate; 38 GPM (8600 L/h) B2HA 112, 399 1 boiler 2 boilers 3 boilers 4 boilers 5 boilers 6 boilers 7 boilers...
  • Page 35: Installation Examples

    They further do not display all system varieties, safety devices, or concepts possible. Specific If a DHW storage tank other than a Viessmann Vitocell system layouts may be further discussed with the local 100 or 300 tank is used, the installer must verify proper Viessmann sales representative office.
  • Page 36: System Layout 1-10

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 1 Vitodens 200-W, B2HA with a direct-connected heating circuit Legend Installation of ... A Vitodens 200-W B2HA boiler with ■ radiator heating circuit (high-temp. circuit) Vitotronic 200, HO1B outdoor reset control DHW production ■...
  • Page 37 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 2 Vitodens 200-W, B2HA with one heating circuit and low-loss header Legend Vitodens 200-W B2HA boiler with Installation of ... Vitotronic 200, HO1B outdoor reset radiator heating circuit (high-temp. circuit) ■...
  • Page 38 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 3 Vitodens 200-W, B2HA with... - DHW storage tank - one heating circuit with mixing valve and system separation Installation of ... Legend Vitodens 200-W B2HA boiler with underfloor heating circuit with 3-way mixing valve ■...
  • Page 39 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 4 Vitodens 200-W, B2HA with... - DHW storage tank - one direct-connected heating circuit - one heating circuit with a mixing valve Legend Installation of different heating circuits...
  • Page 40 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 5 Vitodens 200-W, B2HA with... - DHW storage tank - one heating circuit with mixing valve - one heating circuit without mixing valve and low-loss header Installation of different heating circuits...
  • Page 41 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 6 Vitodens 200-W, B2HA with... - DHW storage tank - one heating circuit without a mixing valve - two heating circuits with a mixing valve - low-loss header Installation of different heating circuits...
  • Page 42 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 7 Vitodens 200-W, B2HA with... - direct-connected heating circuit - one heating circuit with system separation Installation of different heating circuits... Legend radiator heating circuit (high-temp. circuit) ■...
  • Page 43 - low-loss header - multiple heating circuits with mixing valves - one heating circuit without mixing valve When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance. Legend Vitodens 200-W B2HA boiler with Vitotronic *1 Contact your local Sales Representative for details.
  • Page 44 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 9 Vitodens 200-W, B2HA/B2HB with... - DHW storage tank - low-loss header - three zone circuits Installation of different heating circuits... Legend Vitodens 200-W boilers DHW production ■...
  • Page 45 Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation System Layout 10 Multiple (up to eight) Vitodens 200-W, models B2HA 112, 150, 399, 530 with... - multiple heating circuits with mixing valves - low-loss header When designing a multiple Vitodens system as shown...
  • Page 46: Alternative Dhw Connection

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Alternative DHW Connection The following piping diagram reflects an alternative connection for the DHW tank only and applies to system layouts 2, 5, 6 and 8. The boiler control pump logic function must be programmed in the Service Instructions.
  • Page 47: Boiler In Heating/Cooling

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Boiler in Heating/Cooling Boiler in heating/cooling application The boiler, when used in connection with a refrigeration system, must be installed ensuring the chilled medium is piped in parallel to the boiler with appropriate valves to prevent the chilled medium from entering the boiler.
  • Page 48: Boiler With Low Water Cut-Off

    Boiler Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Boiler with Low Water Cut-off Boiler with low water cut-off (remote-mounted, field supplied) Automatic Automatic air vent air vent A low water cut-off may be required by local codes. Do not install an isolation valve between boiler and low water cut-off.
  • Page 49 Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Overview of Electrical Connections, Models B2HA 112, 150, 399 and 530 CAUTION WARNING DISCONNECT POWER BEFORE Label all wires prior to disconnection SERVICING BOILER. when servicing controls. Wiring errors can cause improper and dangerous operation.
  • Page 50: Overview Of Electrical Connections, Models B2Ha 112, 150, 399 And 530

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Overview of Electrical Connections, Models B2HA 112, 150, 399 and 530 (continued) Legend IMPORTANT Outdoor Temperature Sensor Supply Temperature Sensor/Low Loss Header Electrical installations must comply with the latest edition of: Boiler Temperature Sensor/High Limit Sensor In the U.S.A., the National Electrical Code (NEC),...
  • Page 51: Electrical Connections

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Electrical Connections Power supply connection of accessories The power supply connection of accessories can be made directly at the control. The connection is activated and deactivated with the system on/off switch.
  • Page 52: Accessing The X3 Plug

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Accessing the X3 Plug 1. Remove the control unit cover (see page 24). 2. Remove the X3 plug from the control board. Install the required sensors. 3. Reinstall the control cover.
  • Page 53: Connecting The Outdoor Temperature Sensor

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connecting the Outdoor Temperature Sensor 1. Remove cover of outdoor temperature sensor. 2. Mount wall-mount base (cable entry must point downward). IMPORTANT The outdoor temperature sensor should be mounted 6.6 to 8.2 ft.
  • Page 54: External 0-10 Volt Signal Connection

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation External 0-10 Volt Signal Connection 1. Connect the external 0-10 V signal to plug 0-10V located in the extension module EA1. Extension Module EA1 2. Ensure correct polarity. 3. See chart for maximum possible boiler water temperature and required signal.
  • Page 55: Connecting A 24Vac Thermostat

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Connecting a 24 VAC Thermostat 1. Connect normally open dry contact of the switching relay (‘T-T’ contact) to terminal DE1, DE2 or DE3 of the EA1 module located in the boiler electrical junction box.
  • Page 56: Thermostat Connection

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Thermostat Connection Legend Refer to the boiler Installation Instructions for A Room thermostat (dry contact) zone circuit 1 locating and accessing the integrated EA1 module. B Room thermostat (dry contact) zone circuit 2...
  • Page 57: Pump Connection

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Pump Connection Connection to boiler Pump output assignment is done using the start-up wizard. A maximum of 2 zone circuit pumps can be connected to the boiler additional pumps will require the use of an AM1 extension module.
  • Page 58: Lon Module

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation LON Module Installing the LON module to the boiler control board 1. Remove the control cover. 2. Insert the LON module into the boiler control board. 3. Connect the LON connector cable to the LON module.
  • Page 59: Accessory Kit

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Accessory Kit Boiler Accessory kit connections for heating circuit with Control mixing valve The mixing valve controller kit can only be used with wall-mounted gas-fired hot water heating boilers and a weather-responsive control (it can be used as an alternative for a Vitotronic control HK1B).
  • Page 60: Closing The External Accessories Connection Box

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Closing the External Accessory Connection Box 4. Tilt the top of the external accessory connection box cover forward. 5. Drop down over the locating pins and set the cover in place.
  • Page 61: Instructing The System User

    Control Connections Vitodens 200-W B2HA 112, 150, 399, 530 Installation Closing the External Accessory Connection Box (continued) 8. Tighten the external accessory connection box retaining screw. 9. Install the external accessory connection box cover screws. Reinstalling the Front Enclosure Panel 10.
  • Page 62 Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Installation Technical Data Boiler Model No. B2HA 112, 399 150, 530 *A CSA input Natural Gas (NG) 113-399 113-530 (kW) (33-117) (33-155) 113-399 113-530 CSA input Liquid Propane Gas (LPG) (33-117)
  • Page 63 For details refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System. Add approximately 2b inches (65 mm) for coaxial vent pipe transition adaptor. For information regarding other Viessmann System Technology componentry, please reference the documentation of each respective product.
  • Page 64: Installation Fittings

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Installation Installation Fittings Parts 0301 Nipple ¾ in. x 1b in. 0302 Sediment faucet ¾ in. 0303 Tee, ¾ in. 0304 Nipple ¾ in. x 3b in. 0305 Reducing tee 1b in. x 1b in. x ¾ in.
  • Page 65: Lighting And Operating Instructions

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Installation Lighting and Operating Instructions FOR YOUR SAFETY READ BEFORE OPERATING W A R N I N G: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
  • Page 66 Vitodens 200-W B2HA 112, 150, 399, 530 Installation...
  • Page 67 Service Instructions for use by heating contractors Vitodens 200-W, B2HA Models 112, 150, 399, 530 Wall-mounted, gas-fired condensing boiler Natural gas and LPG version For operation with Natural Gas and Liquid Propane Gas Heating input 113 to 530 MBH 33 to 150 kW VITODENS 200-W Product may not be exactly as shown...
  • Page 68 Safety Vitodens 200-W B2HA 112, 150, 399, 530 Service Safety, Installation and Warranty Requirements Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life.
  • Page 69 Safety Vitodens 200-W B2HA 112, 150, 399, 530 Service Safety, Installation and Warranty Requirements (continued) Fiberglass wool and ceramic fiber materials First aid measures - If eye contact occurs, flush eyes with water to WARNING remove dust. If symptoms persist, seek medical attention.
  • Page 70 Table of Contents Vitodens 200-W B2HA 112, 150, 399, 530 Service Page Safety Safety, Installation and Warranty Instructions....2 General Information About these Service Instructions........6 Necessary Tools............6 Important Regulatory and Installation Requirements..7 For installations on the Commonwealth of ............8 Massachusetts CSD-1 Field Testing of High Limit Switches....
  • Page 71 Table of Contents Vitodens 200-W B2HA 112, 150, 399, 530 Service Page Outdoor Reset Programming Unit Start-up and Shutdown..........32 Menu..............32 Zone Circuit Display..........33 Functional Description..........34 Combustion Management Systems......34 Installation Examples..........35 Heating Curve Adjustments........40 Connecting the Boiler Control to a LON System....42 Coding 1 General..............44...
  • Page 72: General Information

    General Information Vitodens 200-W B2HA 112, 150, 399, 530 Service About these Service Instructions Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.
  • Page 73: Important Regulatory And Installation Requirements

    General Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Important Regulatory and Installation Requirements Codes The installation of this unit shall be in accordance with The following topics must be covered: local codes or, in the absence of local codes, use CAN/ Proper system operation sequence.
  • Page 74: For Installations On The Commonwealth Of Massachusetts

    VIESSMANN IS NOT RESPONSIBLE FOR ANY DAMAGES THAT THE FOLLOWING TEST PROCEDURE MAY RESULT IN BY OVERHEATING THE SYSTEM.
  • Page 75: Applicability

    General Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Applicability CAUTION The boiler serial number must be provided when ordering replacement parts. Some replacement parts are not reverse compatible with previous versions of the Vitodens 200-W B2HA boiler. IMPORTANT...
  • Page 76: Mechanical Room

    General Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Mechanical Room During the early stages of designing a new home, we recommend that proper consideration be given to constructing a separate mechanical room dedicated to the gas- or oil-fired heating equipment and domestic hot water storage tank(s).
  • Page 77: Accessing The User Interface Programming Unit

    Start-up and Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Accessing the User Interface Programming Unit 1. Turn up both locks to unlock the user interface programming unit covers. 2. Slide open the user interface programming unit covers. Check Power Supply Connection...
  • Page 78: Start-Up Wizard

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Start-up Wizard Select Language At the commissioning stage, the display is in German. 1. “Sprache” (Language) Deutsch DE (German) 2. Select the required language with 3. Accept by pressing OK Set time and date 1.
  • Page 79 Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Start-up Wizard (continued) Select zone circuits During the start-up wizard an additional display screen will come up asking for the number of connected zone circuits to adjust and press OK. If no zone circuit is selected the control will finish the...
  • Page 80 Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Start-up Wizard (continued) Select pump output Assign desired pump output for zone circuit with press OK. Confirm pump output Confirmation of selected pump output and press OK. Zone circuit temperature setting For the selected zone with fixed set point thermostat will display zone circuit temperature setting.
  • Page 81: Removing Front Enclosure Panel

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Removing Front Enclosure Panel Some of the following service steps require the removal of the front enclosure panel. To avoid personal injury and/or product damage of any kind please follow the instructions below carefully when removing the front enclosure panel.
  • Page 82: Fill Heating System With Water

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Fill Heating System with Water 3. To remove debris and/or sludge ensure that the system piping is flushed out. Failure to do so could cause settlement in the boiler causing overheating and damage not covered by warranty.
  • Page 83: Bleed (Vent) Air From Boiler Heat Exchanger

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Bleed (Vent) Air from Boiler Heat Exchanger 1. Connect hose to boiler filling tap and other end to a fresh water supply (or heating medium). 2. Open fresh water supply valve and then the boiler filling tap slowly (isolation valves must be closed during fill/bleed process).
  • Page 84: Designating Heating Circuits

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Designating Heating Circuits In the delivered condition, the heating circuits are designated "Heating circuit 1", "Heating circuit 2" and "Heating circuit 3" (if installed). If the system user prefers, the heating circuits can be designated differently to suit the specific system.
  • Page 85: Convert Fuel Type To Liquid Propane Gas

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Convert Fuel Type to Liquid Propane Gas 1. Set adjusting screw A at the gas valve to “2” (using a hex key, 2.5 mm). Note: The Vitodens 200-W, B2HA boiler comes factory adjusted for operation with natural gas.
  • Page 86: Measure Static Pressure And Running Pressure

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Measure Static Pressure and Running Pressure 1. To measure static and/or running pressure remove boiler enclosure panel as indicated page 15 in these instructions. 2. Close gas shutoff valve (field supplied).
  • Page 87: Pressure Switches

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Pressure Switches Rear View GDW1 low pressure gas switch (n.c.) When the gas pressure rises above 4” w.c. the switch will open and the burner will operate. When the gas pressure drops below 4” w.c. the switch will close and the boiler control will shut off the burner.
  • Page 88: Sequence Of Operation And Potential Faults During Each Start-Up Cycle

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Sequence of Operation and Potential Faults During Each Start-up Cycle Display message Measures Increase set value and ensure Call for heat by control heat is drawn off Fan starts up After approx.
  • Page 89: Set Maximum Input

    Start-up Vitodens 200-W B2HA 112, 150, 399, 530 Service Set Maximum Input The maximum input (or output) for heating operation can be limited. The limit is set via the modulation range. The maximum adjustable heating input (or output) is limited upwards by the boiler coding card.
  • Page 90: Check Coaxial Venting System For Leaks

    Start-up and Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Check Coaxial Venting System for Leaks (circular air gap measurement) Viessmann strongly recommends that the heating contractor perform a simplified leak test during boiler start-up. For this purpose it is sufficient to measure...
  • Page 91: Checking The Flue Gas Flapper

    Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Checking the Flue Gas Flapper 1. Undo three screws and remove fan A. 2. Remove the flue gas flapper B. 3. Check the flapper and gasket for dirt and damage. Replace as necessary.
  • Page 92: Check And Adjust Ignition And Ionization Electrodes

    Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Check and Adjust Ignition and Ionization Electrodes 1. Check the ignition electrodes A and ionization electrode B for wear and contamination. 2. Clean electrodes with small brush (not a wire brush) or emery paper (cloth).
  • Page 93: Check Condensate Drain

    Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Check Condensate Drain Cleaning condensate trap (during regular maintenance) Remove rubber cap D from below the condensate trap. Unscrew threaded cap E from the condensate trap C. Note: After unscrewing the threaded cap E it may be necessary to pry off to remove.
  • Page 94: Check Neutralization Unit (If Applicable)

    Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Check Neutralization Unit (if applicable) 1. Check the pH value of the condensate with pH measuring strip. If the pH value is less than 6.5, replace granulate. 2. If contaminated: Rinse neutralization unit with tap water.
  • Page 95: Check Functioning Of Safety Valves

    Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Check Functioning of Safety Valves Ensure proper operation of low water cut-off(s) (if applicable), pressure relief valve, and pump(s). Check pressure gage, air vent and pressure relief valve. Ensure that pressure relief valve does not leak and that it operates in accordance with information provided by the manufacturer.
  • Page 96: Clock Natural Gas Meter

    Service Vitodens 200-W B2HA 112, 150, 399, 530 Service Clock Natural Gas Meter Clock natural gas meter to verify input. Ensure all other gas equipment served by the meter is turned off during timing of gas input to the Vitodens 200-W, B2HA boiler.
  • Page 97: Check Co 2 Setting

    1. Connect a flue gas analyzer to test port A at boiler the Combustion Management System developed by vent pipe adaptor. Viessmann which ensures optimal combustion quality 2. Open gas shut-off valve, start up boiler and create independent of gas quality and type. (For a description of heat demand.
  • Page 98: Start-Up And Shutdown

    Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Start-up and Shutdown Starting the heating system 1. Check the heating system pressure at the pressure gauge. The heating system pressure is too low if the indicator points to the area below 15 psi.
  • Page 99: Zone Circuit Display

    Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Menu (continued) Symbols on the display These symbols are not always displayed, but appear subject to the system version and the operating state. Heating programs 9 Standby mode with frost protection monitoring...
  • Page 100: Functional Description

    Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Functional Description Domestic hot water supply with gas-fired space heating Space heating mode boiler The control unit calculates a boiler water setpoint Domestic hot water heating is activated when the tank temperature based on the outdoor or room temperature temperature is 4.5ºF (2.5ºC) below the tank temperature...
  • Page 101: Installation Examples

    Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Installation Examples System type 1 Matching the control unit to the heating system System Examples for codes 00:1 and 00:2 The control unit must be matched to the equipment Heating system with one heating circuit without mixing level of the system.
  • Page 102 Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Installation Examples (continued) System type 2 System Examples for codes 00:3 and 00:4 Heating system with one heating circuit with mixing valve M2 with system separation, with/without DHW heating, with/without low loss header.
  • Page 103 Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Installation Examples (continued) System type 3 System Examples for code 00:5 and 00:6 Heating system with one heating circuit without mixing valve, one heating circuit with mixing valve, one heating...
  • Page 104 Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Installation Examples (continued) System type 4 System Example for code 00:7 and 00:8 Heating system with one heating circuit with mixing valve, one heating circuit with mixing valve M2 (with...
  • Page 105 Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Installation Examples (continued) System type 6 Function/system components Code Heating system with three zone circuits (thermostat Adjust Group operated). Zone circuit 1 A1 (AM1) 33:5 General/2 Zone circuit 2 A2 (AM1)
  • Page 106: Heating Curve Adjustments

    Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Curve Adjustment The heating curves represent the relationship between The supply temperature that is required to achieve a given the outdoor temperature and the boiler water or supply room temperature depends on the heating system and temperature.
  • Page 107 Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Curve Adjustment (continued) Changing the slope and level Extended menu: 2. Select “Heating” - OK 3. Heating circuit selection 4. Accept with OK 5. Heating curve - OK 6.
  • Page 108: Connecting The Boiler Control To A Lon System

    Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Connecting the Boiler Control to a LON System Updating the LON participant list Scanning and resetting the “Service” display Only possible if all participants are connected and the After the limits specified in coding addresses “21”...
  • Page 109 Outdoor Reset Programming Unit Vitodens 200-W B2HA 112, 150, 399, 530 Service Connecting the Boiler Control to a LON System (continued) The LON communication module (accessory) must be connected. Note: The data transfer via the LON can take several minutes.
  • Page 110: General

    Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service General Calling up coding level 1 2. “Coding level 1” 3. Select group of required coding address: Note: Codes are displayed as plain text. - “General” Codes that have no function due to the heating - “Boiler”...
  • Page 111 Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Coding in the factory set mode Possible change Internal circulation pump function 51:0 System with low loss header: 51:1 System with low loss header: Internal circulation pump always...
  • Page 112: Boiler

    Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service Boiler Select “Boiler” Coding in the factory setting Possible change Single/multi boiler system 01:1 Single boiler system 01:2 Multi boiler system with Vitotronic 300-K, control. Boiler number 07:1 Boiler number in multi boiler...
  • Page 113: Solar

    Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service Solar Select “Solar” Note: The solar group is only displayed if a solar control module, type SM1, is connected. Coding Coding in the factory setting Possible change Speed control solar circuit pump...
  • Page 114 Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 Select “Heating circuit ...” Coding Coding in the factory setting Possible change Priority DHW heating A2:2 DHW tank priority applicable to A2:0 Without DHW tank priority...
  • Page 115 Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change Extended economy function mixing valve A7:0 Without mixing valve economy A7:1 With mixing valve economy function...
  • Page 116: Heating Circuit 1, 2 And 3

    Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change Minimum flow temperature heating circuit C5:20 Electronic minimum flow temp. C5:1 Minimum limit adjustable from limit 68°F (20°C) 34 to 260°F (1 to 127°C)
  • Page 117 Coding 1 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change Pump control in “Only DHW” F6:25 In the “Only DHW” operating F6:0 In the “Only DHW” operating...
  • Page 118: General

    Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General If the heating circuits were given individual designations, Calling up coding level 2 the selected designation and “HC1”, “HC2” or “HC3” Note: At coding level 2, all codes are accessible, appear instead: including the codes at coding level 1.
  • Page 119 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Value address System type Description 00: ... One heating circuit with mixing valve M2 (heating circuit 2) and one heating circuit with mixing valve M3 (heating circuit 3), without DHW heating.
  • Page 120 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Coding in the factory setting Possible change 33:1 Function output A1 at 33:0 Function output A1: DHW extension AM1: Heating recirculation pump. circuit pump 33:2 Function output A1: Circulation pump for DHW tank heating.
  • Page 121 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Coding in the factory setting Possible change 3A:0 Function input DE1 at 3A:1 Function input DE1: Heating extension program - changeover. EA1: Not assigned 3A:2 Function input DE1: External demand with set flow temperature.
  • Page 122 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Coding in the factory setting Possible change 3C:0 Function input DE3 at extension 3C:1 Function input DE3: Heating EA1: Not assigned program - changeover. 3C:2 Function input DE3: External demand with set flow temperature.
  • Page 123 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Coding in the factory setting Possible change 51:0 System with low loss header: 51:1 System with low loss header: Boiler circuit pump is always When there is heat demand, the...
  • Page 124 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Coding in the factory setting Possible change 77:1 LON participant number 77:2 LON participant number, adjustable from 1 to 99: 77:99 1 - 8 = Boiler 9 = Cascade...
  • Page 125 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service General (continued) Coding in the factory setting Possible change 8A:175 DO NOT ADJUST 8F:0 Operation in the standard 8F:1 Operation in the standard menu and extended menu and extended menu menu enabled blocked.
  • Page 126: Boiler

    Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Boiler Select “Boiler” Coding Coding in the factory setting Possible change 01:1 Single boiler system 01:2 Multi boiler system with Vitotronic 300-K. 04:1 Minimum burner pause subject to the 04:0...
  • Page 127: Dhw

    Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Select “DHW” Coding Coding in the factory setting Possible change 56:0 Set DHW temperature 56:1 Set DHW temperature adjustable adjustable from 50 to 140°F from 50 to over 140°F (10 to (10 to 60°C)
  • Page 128 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service (continued) Coding in the factory setting Possible change 63:0 Without auxiliary function for 63:1 Auxiliary function: 1 x daily NOT USED DHW heating 63:2 Every 2 days to every 14 days.
  • Page 129: Solar

    Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Solar Select “Solar” Note: The solar group is only displayed if a solar control module, type SM1, is connected. Coding Coding in the factory setting Possible change 00:8 The solar circuit pump starts...
  • Page 130 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Solar (continued) Coding in the factory setting Possible change 09:130 The solar circuit pump stops 09:20 Temperature adjustable from if the collector temperature 68 to 392°F (20 to 200°C). reaches 266°F (130°C)
  • Page 131 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Solar (continued) Coding in the factory setting Possible change 11:50 Set DHW tank temperature for 11:10 The set DHW tank temperature for solar 122°F (50°C). solar can be adjusted from 50 to...
  • Page 132 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Solar (continued) Coding in the factory setting Possible change 23:4 Stop temperature differential 23:2 Stop temperature differential for central heating for central heating backup is backup: 4 K. 23:30 adjustable from 1 to 29 K.
  • Page 133 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 Select “Heating circuit ...” Coding Coding in the factory setting Possible change A0:0 Without remote control A0:1 With Vitotrol 200A (automatic recognition). A0:2 With Vitotrol 300A or Vitohome 300 (automatic recognition).
  • Page 134 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change A4:0 With frost protection A4:1 No frost protection; this setting is only possible if code “A3:-9” has been selected.
  • Page 135: Heating Circuit 1, 2 And 3

    Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change A8:1 Heating circuit with mixing valve A8:0 Heating circuit with mixing valve creates a demand for the boiler...
  • Page 136 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change C5:20 Electronic minimum flow C5:1 Minimum limit adjustable from 1 to temperature limit 68°F 260°F (127°C) (limited by boiler- (20°C)
  • Page 137 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change E5:0 Do not adjust E6:... Maximum speed of the variable E6:0 Maximum speed adjustable speed heating circuit pump in from 0 to 100%.
  • Page 138 Coding 2 Vitodens 200-W B2HA 112, 150, 399, 530 Service Heating Circuit 1, 2 and 3 (continued) Coding in the factory setting Possible change F7:25 In the “Standby” operating F7:0 In the “Standby” operating mode, the circulation pump in mode, the circulation pump in the...
  • Page 139: Calling Up The Service Level

    Diagnosis and Service Scans Vitodens 200-W B2HA 112, 150, 399, 530 Service Calling up the Service Level Note: Do not adjust menu item “Multi-boiler system”. Press OK and simultaneously for approximately 4 The menu item turns a weather-compensated seconds. control unit into a constant temperature control Service menu overview unit.
  • Page 140: Diagnosis

    Diagnosis and Service Scans Vitodens 200-W B2HA 112, 150, 399, 530 Service Diagnosis The following values can be scanned, depending on the system installed: Display screen Explanation Slope A1 - shift A1 Slope M2 - shift M2 Outdoor temperature adjustment...
  • Page 141 Diagnosis and Service Scans Vitodens 200-W B2HA 112, 150, 399, 530 Service Diagnosis (continued) For an explanation of the relevant values in the individual lines and fields, see the following table: Line Field (brief scan) Heating circuit A1 Heating circuit M2...
  • Page 142: Checking Outputs (Relay Test)

    Diagnosis and Service Scans Vitodens 200-W B2HA 112, 150, 399, 530 Service Checking Outputs (Relay Test) 1. Press OK and simultaneously for approximately 4 seconds. 2. “Actuator test” The following relay outputs can be controlled subject to system design: Display...
  • Page 143: Fault Display

    Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Fault Display In the event of a fault, red fault indicator A flashes. Acknowledging a fault  “ “ flashes on the display and “Fault” is shown. Follow the instructions on the display.
  • Page 144 Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Fault Codes (continued) Fault code Detailed fault System behavior*1 Cause Corrective action on display code*2 Burner blocked Short circuit on boiler Check the boiler water water temperature temperature sensor sensor (see page 86).
  • Page 145 Troubleshooting Fault Codes (continued) Fault code Detailed fault System behavior*1 Cause Corrective action on display code*2 No solar DHW heating Tank temperature Check temperature sensor % sensor % cable broken on solar control module. Control mode No flow rate in collector Check solar circuit circuit or flow rate too pump and solar circuit.
  • Page 146 Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Fault Codes (continued) Fault code Detailed fault System behavior*1 Cause Corrective action on display code*2 Control mode without remote Communication error, Check connections, cable, control remote control Vitotrol coding address “A0” in “Heating heating circuit 2 circuit”...
  • Page 147 Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Fault Codes (continued) Fault code Detailed fault System behavior*1 Cause Corrective action on display Code*2 Control mode Input DE3 reports a Remove fault at appliance fault at extension EA1 concerned. Control mode without...
  • Page 148 Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Fault Codes (continued) Fault code Detailed fault System behavior*1 Cause Corrective action on display code*2 Burner blocked Fault, supply voltage Replace the control unit. Burner blocked Fault flame amplifier Replace control unit.
  • Page 149 Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Fault Codes (continued) Fault code Detailed fault System behavior*1 Cause Corrective action on display code*2 Burner in a fault mode At burner start, flame Check gas supply (gas pressure signal is missing or too and gas regulator).
  • Page 150 Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Fault Codes (continued) Fault code Detailed fault System behavior*1 Cause Corrective action on display code*2 Burner in fault mode Fan speed too low Check the fan, the fan cables during burner start and power supply.
  • Page 151: Corrective Action

    Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Corrective Action Continuous boiler pump operation When the Vitodens 200 B2HA boiler is switched from a single boiler operation to a multi-boiler operation, coding addresses 30:0 may automatically reset to 30:3. This will result in the boiler pump operating continuously.
  • Page 152: Checking The Boiler Temperature Sensor And Fixed High Limit, Dhw Tank Temperature Sensor Or Flow Temperature Sensor For The Low Loss Header

    Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Corrective Action (continued) Checking the boiler temperature sensor and fixed high limit, DHW tank temperature sensor or flow temperature sensor for the low loss header 1. Boiler temperature sensor: Remove lead to boiler water temperature sensor §...
  • Page 153: Replacing The Flow Rate Sensor

    Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Corrective Action (continued) Replacing the flow rate sensor Note: In the event of a fault, both sensors need to be replaced. 1. Drain the boiler on the heating water side. 2. Pull leads from flow rate sensor A.
  • Page 154: Extension Kit For Heating Circuit With Mixing Valve

    Troubleshooting Vitodens 200-W B2HA 112, 150, 399, 530 Service Corrective Action (continued) Extension kit for heating circuit with mixing valve Checking the setting of rotary selector S1: Heating circuit Rotary selector S1 setting The rotary selector on the PCB of the extension kit Heating circuit with mixing defines the assignment to the relevant heating circuit.
  • Page 155: External Extensions Am1 (Accessory)

    Function Description Vitodens 200-W B2HA 112, 150, 399, 530 Service External Extensions AM1 (accessory) Functions One of the following circulation pumps can be connected Select the output functions by means of the codes on to each of the connections A1 and A2: the boiler control unit.
  • Page 156: Internal Extensions Ea1

    Function Description Vitodens 200-W B2HA 112, 150, 399, 530 Service Internal Extensions EA1 Legend Refer to main wiring diagram on page 95. Fuse Digital input 1 Digital input 2 Digital input 3 0 – 10V 0 - 10V input fÖ...
  • Page 157 Function Description Vitodens 200-W B2HA 112, 150, 399, 530 Service Internal Extensions EA1 (continued) Digital data inputs DE1 to DE3 Effect of the external demand function on the pumps The following functions can be connected alternatively: The effect on the internal circulation pump is selected in coding address 3F in the “General”...
  • Page 158: Control Functions

    Function Description Vitodens 200-W B2HA 112, 150, 399, 530 Service Control Functions External heating program changeover External blocking The “External heating program changeover” function is The “External blocking” and “External blocking and fault connected via input “EA1” in the EACB.
  • Page 159 Function Description Vitodens 200-W B2HA 112, 150, 399, 530 Service Control Functions (continued) Venting program Reducing the heat-up time During the transition from operation with reduced During the venting program, the circulation pump will room temperature to operation with standard room...
  • Page 160 Function Description Vitodens 200-W B2HA 112, 150, 399, 530 Service Control Functions (continued) Raising the reduced room temperature Allocating heating circuits to the remote control During operation with reduced room temperature, the The heating circuit allocation must be configured when reduced room setpoint temperature can be automatically commissioning the Vitotrol 200A or Vitotrol 300A.
  • Page 161: Wiring Diagram

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Wiring Diagram CAUTION WARNING DISCONNECT POWER BEFORE Label all wires prior to disconnection SERVICING BOILER. when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation If any of the original wires as after servicing.
  • Page 162 Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Wiring Diagram (continued) Legend IMPORTANT Outdoor Temperature Sensor Supply Temperature Sensor/Low Loss Header Electrical installations must comply with the latest edition of: Boiler Temperature Sensor/High Limit Sensor In the U.S.A., the National Electrical Code (NEC),...
  • Page 163: Burner Program Sequence Of Operation

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Burner Program Sequence of Operation Phase 0: Stand-by Phase 6: Burner modulation operation or calibration Complete shutdown until the next call for heat. In this At the end of the flame stabilization period (4.5 seconds.),...
  • Page 164: Parts List

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Parts Lists Model No. Serial No. B2HA 112, 399 Boiler 7510835 B2HA 150, 530 Boiler 7510836 Ordering Replacement Parts: Please provide model no. from rating plate A and serial no. when ordering replacement parts. Order replacement components from your Viessmann distributor.
  • Page 165 Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Parts Lists (continued) Model No. Serial No. B2HA 112, 399 Boiler 7510835 B2HA 150, 530 Boiler 7510836 Ordering Replacement Parts: Please provide model no. from rating plate and serial no.
  • Page 166 Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Parts Lists (continued) Model No. Serial No. B2HA 112, 399 Boiler 7510835 B2HA 150, 530 Boiler 7510836 Ordering Replacement Parts: Please provide model no. from rating plate and serial no.
  • Page 167 Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Parts Lists (continued) Model No. Serial No. B2HA 112, 399 Boiler 7510835 B2HA 150, 530 Boiler 7510836 Ordering Replacement Parts: Please provide model no. from rating plate and serial no.
  • Page 168 Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Parts Lists (continued) Model No. Serial No. B2HA 112, 399 Boiler 7510835 B2HA 150, 530 Boiler 7510836 Ordering Replacement Parts: Please provide model no. from rating plate and serial no.
  • Page 169: Technical Data

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Technical Data Boiler Model No. B2HA 112, 399 150, 530 *A CSA input Natural Gas (NG) 113-399 113-530 (kW) (33-117) (33-155) 113-399 113-530 CSA input Liquid Propane Gas (LPG) (33-117)
  • Page 170 For details refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System. Add approximately 2b inches (65 mm) for coaxial vent pipe transition adaptor. Optional low NOx certified by SCAQMD Natural Gas models available. For information regarding other Viessmann System Technology componentry, please reference the documentation of each respective product.
  • Page 171: Maintenance Record

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Maintenance Record...
  • Page 172: Lighting And Operating Instructions

    Additional Information Vitodens 200-W B2HA 112, 150, 399, 530 Service Lighting and Operating Instructions FOR YOUR SAFETY READ BEFORE OPERATING W A R N I N G: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
  • Page 173 Vitodens 200-W B2HA 112, 150, 399, 530 Service...
  • Page 174 Vitodens 200-W B2HA 112, 150, 399, 530 Service...
  • Page 176 Product may not be exactly as shown IMPORTANT Certified as a component Read and save these instructions part for Viessmann boilers for future reference. Please file in Service Binder 5547 199 - 05 08/2017...
  • Page 177 Follow the manufacturing facilities. Viessmann maintenance schedule of the boiler contained in this manual. Contaminated combustion air will damage the boiler and may lead to substantial property damage, severe Operating and Service Documentation personal injury and/or loss of life.
  • Page 178 Table of Contents Vitotronic 200 Operating Page General Safety, Installation and Warranty Requirements....2 Safety About these Instructions..........4 For your Safety............4 Where to Find the Controls..........7 Controls, Vitotronic 200..........7 How to use the Controls, Vitotronic 200.......7 Central Heating Controls Overview............8 Start-up/Standby/Shutdown.........9 Further Adjustments Setting the Display Contrast........10 Setting the Display Brightness........10...
  • Page 179: About These Instructions

    Regular inspection and service by a qualified heating - Operating Instructions Vitotronic 300-K MW2C contractor is important to the performance of the Viessmann Vitodens 200-W and Vitocrossal 300 CU3A. Neglected maintenance impacts on warranty; regular inspection ensures clean, environmentally friendly and efficient operation.
  • Page 180 Flue products contain poisonous carbon monoxide gas which can cause nausea or asphyxiation Note: Viessmann does not test any detectors and makes resulting in severe personal injury or loss of life. no representation regarding any brand or type of detector.
  • Page 181 Safety Vitotronic 200 Operating Frozen water pipe hazard Installation area conditions WARNING WARNING Failure to protect against frozen pipes could result in Incorrect ambient conditions can lead to damage to burst water pipes, serious property damage and/or the heating system and put safe operation at risk. personal injury.
  • Page 182: Where To Find The Controls

    Operation Vitotronic 200 Operating Where to Find the Controls Each boiler is equipped with its own control unit for constant temperature operation. These control units are regulated by a higher weather- compensated cascade control unit. H Control unit in constant temperature mode on the boiler: Vitotronic 200 Controls, Vitotronic 200 ...
  • Page 183: Controls Overview

    Central Heating Vitotronic 200 Operating Controls Overview Vitodens 200-W controls with side panels open Legend A Fault indicator (red) B ON indicator (green) C Reset button D ON/OFF switch E Pressure gauge (pressure display) F Vitotronic 200, type HO1B user interface Vitocrossal 300 CU3A controls with panel covers open Legend A Vitotronic 200, type HO1B user interface...
  • Page 184: Start-Up/Standby/Shutdown

    Central Heating Vitotronic 200 Operating Start-up/Standby/Shutdown Starting the heating system Placing each boiler in standby with frost protection 1. Check the heating system pressure at the pressure monitoring gauge. The system pressure is too low if the indicator is below 14 psi. In this case, top up with water or At the relevant Vitotronic 200, press the following keys: notify your local heating contractor.
  • Page 185: Setting The Display Contrast

    Further Adjustments Vitotronic 200 Operating Setting the Display Contrast Extended menu: 2. “Settings” 3. “Contrast” 4. Set the required contrast. Setting the Display Brightness If you would like the texts in the menu to be more clearly legible, change the brightness for “Control”. You can also alter the screen saver brightness.
  • Page 186: Setting The Time And Date

    Further Adjustments Vitotronic 200 Operating Setting the Time and Date The time and date are factory-set. If your heating system has been shut down for a long time, it may be necessary to set the time and date. Extended menu: 2.
  • Page 187: Calling Up The Service Level

    Further Adjustments Vitotronic 200 Operating Calling up the Service Level Note: Do not adjust menu item “Multi-boiler system”. Press OK and simultaneously for approximately 4 The menu item turns a constant temperature seconds. control unit into a weather-compensated control unit. Service menu overview Service General...
  • Page 188 Scanning Options Vitotronic 200 Operating Diagnosis Brief scan In the brief scan, you can call up temperatures, software versions and connected components, for example. 1. Press OK and simultaneously for approximately 4 seconds. 2. “Diagnosis” 3. “Brief scan”. Press OK. The display shows 9 lines with 6 fields each. The following values can be scanned, depending on the system installed: Display screen...
  • Page 189: Checking Outputs (Relay Test)

    Scanning Options Vitotronic 200 Operating Checking Outputs (Relay Test) 1. Press OK and simultaneously for approximately 4 seconds. 2. “Actuator test” The following relay outputs can be controlled subject to system design: Display Explanation All actuators All actuators are off. Base load Burner operated at minimum output;...
  • Page 190: Scanning Service Messages

    Scanning Options Vitotronic 200 Operating Scanning Service Messages If your heating system is due for a service, the symbol After a certain number of burner hours run, e.g. 05500 h “ “ flashes on the Vitotronic 200 display, and the following displays are shown.
  • Page 191: Emissions Test Mode

    Scanning Options Vitotronic 200 Operating Emissions Test Mode Emissions test mode for testing flue gas with boiler water Press the following keys: temperature raised briefly. This test mode should only be activated by your service technician during the annual “test mode”. inspection.
  • Page 192: Off" Is Displayed At The Vitotronic 200

    Troubleshooting Vitotronic 200 Operating “OFF” is Displayed at the Vitotronic 200 Cause Remedy The heating program is enabled or the boiler is shut Set the heating program down externally. If necessary, notify your heating contractor. “ ” is Displayed at the Vitotronic 200 Cause Remedy The time for a service, as specified by your heating...
  • Page 193: Maintenance

    Replace only with Your heating system must be serviced by an authorized Viessmann cables. Contact your local heating contractor. contractor at least every 2 years. For this, we advise you to arrange an inspection and maintenance contract with your local heating contractor.
  • Page 194 Vitotronic 200 Operating...
  • Page 195 Vitotronic 200 Operating Quick Reference °C °F +10 +50 +16 +61 +25 +77 +40 +104 +122 +140 +158 +176 +194 +100 +212 +110 +230...