Boiler - Viessmann Vitodens 200-W B2HA 112 Installation Instructions Manual

Wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 112:
Table of Contents

Advertisement

Coding 2

Boiler

Select "Boiler"
Coding
Coding in the factory setting
01:1
Single boiler system
04:1
Minimum burner pause subject to the
boiler load (specified by boiler coding
card)
06:...
Maximum limit of the boiler water
temperature, specified
in °C by the boiler coding card
07:1
Boiler number in multi boiler systems
08:...
Maximum burner heating output in kW
in the case of a multi boiler system
0D:0
DO NOT ADJUST
0E:0
DO NOT ADJUST
13:1
DO NOT ADJUST
14:1
DO NOT ADJUST
15:1
DO NOT ADJUST
21:0
No service interval (hours run) selected 21:1
23:0
No time interval for burner service
24:0
No "Service" display
28:0
No burner interval ignition
2E:0
DO NOT ADJUST
2F:0
Venting program/fill program disabled
30:0
Boiler circulation pump without
variable speed (for use with single
boiler systems with Low Loss Header,
or multi-boiler systems)
31:...
Set speed in % of the internal
circulation pump when operated as
boiler circuit pump, specified by the
boiler coding card
38:0
Status burner control unit: Operational
(no fault)
60
Vitodens 200-W B2HA 112, 150, 399, 530 Service
Possible change
01:2
Multi boiler system with Vitotronic 300-K.
04:0
Minimum burner pause set permanently
(specified by boiler coding card).
06:20
Maximum limit of the boiler water
to
temperature within the ranges specified
06:127
by the boiler.
07:2
Boiler number 2 to 8 in multi- boiler
to
systems.
07:8
08:0
Maximum burner heating output
to
adjustable from 0 to 199 kW
08:199
(limited by boiler specific parameters)
in steps of 1 kW.
--
--
--
--
--
Number of hours run before the burner
to
should be serviced is adjustable from 100
21:100
to 10,000 h
One adjusting step ≙ 100 h.
23:1
Interval adjustable from 1 to 24 months.
to
23:24
24:1
"Service" display (the address is
automatically set and must be manually
reset after a service has been carried
out).
28:1
Interval adjustable from 1 hour
to
to 24 hours. The burner is force started
28:24
for 15 seconds (only when operating
with LPG).
--
2F:1
Venting program enabled.
2F:2
Fill program enabled.
30:1
Boiler variable speed circulation pump
(automatic adjustment).
DO NOT ADJUST
30:2
Boiler variable speed circulation pump
with flow control.
DO NOT ADJUST
30:3
Boiler variable speed circulation pump
controlled via 0-10VDC output [147]
When changing from a single boiler
to a multiboiler operation, the coding
address may automatically reset to
30:3. To prevent continuous boiler pump
operation, adjust the coding address for
each boiler to 30:0.
31:0
Set speed adjustable from
to
0 to 100%.
31:100
38:≠0
Status burner control unit: Fault.
--
--
--
--
--
--