Viessmann Vitodens 200-W B2HA 100 Technical Data Manual
Viessmann Vitodens 200-W B2HA 100 Technical Data Manual

Viessmann Vitodens 200-W B2HA 100 Technical Data Manual

Hide thumbs Also See for Vitodens 200-W B2HA 100:

Advertisement

Technical Data Manual
Model Nos. and pricing: see Price List
Gas-fired wall-mounted condensing boiler
104 to 530 MBH (30 to 155 kW)
Multi-boiler installation 104 to 4240 MBH
For Natural Gas and Liquid Propane Gas
VITODENS
200-W
r
Product may not be exactly as shown
Vitodens 200-W
Series B2HA Series, Models 100, 112 and 150
Gas-Fired Wall-Mounted Condensing Boiler
with modulating MatriX cylinder burner
for room air independent operation
(using a direct vent system or room air
dependent operation).
H
5683 718
- 02 03/2014

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann Vitodens 200-W B2HA 100

  • Page 1 Technical Data Manual Model Nos. and pricing: see Price List Gas-fired wall-mounted condensing boiler 104 to 530 MBH (30 to 155 kW) Multi-boiler installation 104 to 4240 MBH For Natural Gas and Liquid Propane Gas VITODENS 200-W Product may not be exactly as shown Vitodens 200-W Series B2HA Series, Models 100, 112 and 150 Gas-Fired Wall-Mounted Condensing Boiler...
  • Page 2: Product Information

    Product Information Vitodens 200-W B2HA 100 to 150 Technical Data Vitodens 200-W Equipped with the industry’s first intelligent combustion management system and powerful control technology, the new generation Vitodens 200-W gas-fired wall-mount condensing boiler delivers unparalleled performance, reliability and comfort.
  • Page 3: Cross Section

    Product Information Vitodens 200-W B2HA 100 to 150 Technical Data Cross-Section Vitodens 200-W B2HA 100 112, 150 A Inox-Radial heat exchanger made from stainless steel – for high operational reliability and a long service life. Large heating output in the smallest of spaces...
  • Page 4: Technical Data

    Technical Data Vitodens 200-W B2HA 100 to 150 Technical Data Technical Data Boiler Model No. B2HA 100*A 150*A Natural Gas / Liquid Propane Gas CSA input 104-352 113-399 113-530 30-103 33-117 33-155 CSA output *3 98-333 103-375 103-495 29-98 30-110...
  • Page 5 For details refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System. Add approximately 2b inches (65 mm) for coaxial vent pipe transition adaptor. For information regarding other Viessmann System Technology componentry, please reference the documentation of each respective product.
  • Page 6: Dimensional Information

    Dimensional Information Vitodens 200-W B2HA 100 to 150 Technical Data Model B2HA 100 Legend Boiler Supply Gas Connection, 1” NPTF Boiler Return Recommended height (single boiler system) Condensate drain...
  • Page 7 Dimensional Information Vitodens 200-W B2HA 100 to 150 Technical Data Models B2HA 112, 150 Legend Boiler Supply Gas Connection, 1” NPTF Boiler Return Recommended height (single boiler system) Condensate drain...
  • Page 8: Recommended Minimum Service Clearances

    Minimum Clearances Vitodens 200-W B2HA 100 to 150 Technical Data Recommended Minimum Service Clearances Minimum Clearances to Combustibles Front Rear Left Right Vent pipe *1 0 0 AL, CL AL= Alcove CL= Closet Refer to the Installation Instructions of the Vitodens 200-W, B2HA Venting System for details.
  • Page 9: Waterside Flow (Primary Circuit)

    Waterside Flow Vitodens 200-W B2HA 100 to 150 Technical Data Waterside Flow (primary circuit) The Vitodens 200-W, B2HA is designed for closed loop, A low-loss header offers additional benefits not provided forced circulation hot water heating systems only. Use by a pair of closely spaced tees. Viessmann therefore standard friction loss method for pipe sizing.
  • Page 10: Typical System Flow Rates

    System Flow Rates Vitodens 200-W B2HA 100 to 150 Technical Data Typical System Flow Rates Boiler B2HA 100 maximum flow rate; 25 GPM (5700 L/h) Model B2HA 100 1 boiler 2 boilers 3 boilers 4 boilers 5 boilers 6 boilers...
  • Page 11: Heating Circuit / Boiler Pumps

    Pump Information Vitodens 200-W B2HA 100 to 150 Technical Data Heating Circuit / Boiler Pumps Viessmann offers a variety of Grundfos heating circuit Before using the following pumps for a DHW tank / boiler pumps which meet typical Vitodens system application, find out the proper pressure drop through the installation requirements (see “Heating circuit pump...
  • Page 12 Low-Loss Header Information Vitodens 200-W B2HA 100 to 150 Technical Data Low-Loss Header Application Sizing of Low-Loss Header in a Residential/Commercial Single-Boiler Application Boiler No. of Boiler Total Typical System Flow Rates Viessmann Low-loss Model Boilers Max. Flow Temp. Flow...
  • Page 13 Low-Loss Header Information Vitodens 200-W B2HA 100 to 150 Technical Data Low-Loss Header Application (continued) Sizing of Low-Loss Header in a Residential/Commercial Single-Boiler Application Boiler No. of Boiler Total Typical System Flow Rates Viessmann Low-loss Model Boilers Max. Flow Temp.
  • Page 14 Low-Loss Header Information Vitodens 200-W B2HA 100 to 150 Technical Data Low-Loss Header Application (continued) Sizing of Low-Loss Header in a Residential/Commercial Single-Boiler Application Boiler No. of Boiler Total Typical System Flow Rates Viessmann Low-loss Model Boilers Max. Flow Temp.
  • Page 15: Domestic Hot Water Production

    DHW Production Vitodens 200-W B2HA 100 to 150 Technical Data Domestic Hot Water Production For the connection of a stand-alone DHW tank, Vitodens 200-W boilers can be used in conjunction installation fittings (field supplied), an external circulating with the stand-alone DHW storage tanks offered by pump for DHW production (field supplied) and a DHW Viessmann.
  • Page 16: Domestic Hot Water Recirculation

    DHW Recirculation/ Boiler Mounting Vitodens 200-W B2HA 100 to 150 Technical Data Domestic Hot Water Recirculation Vitocell-V stand-alone DHW storage tank DHW recirculation lines increase the level of comfort and convenience of the domestic hot water supply and reduce water consumption.
  • Page 17: Boiler Mounting

    Boiler Mounting Vitodens 200-W B2HA 100 to 150 Technical Data Model B2HA 100 Wall Mount Fitting the wall mounting bracket See the installation instructions applicable to the mounting bracket on each type of material. CAUTION Whichever mounting method is used, ensure that the bracket is tightly and securely fastened to wall.
  • Page 18 Boiler Mounting Vitodens 200-W B2HA 100 to 150 Technical Data Boiler Stand for B2HA 100 The boiler stand is used for free-standing installation of a single boiler within the mechanical room. When using the boiler stand, ensure that the stand is...
  • Page 19 Boiler Mounting Vitodens 200-W B2HA 100 to 150 Technical Data Model B2HA 100 Stand Mount The Vitodens 200-W, model B2HA does not come with a mounting template. The wall location for the frame, mounting bracket and all vents must be field calculated.
  • Page 20 Boiler Mounting Vitodens 200-W B2HA 100 to 150 Technical Data Models B2HA 112, 150 The Vitodens 200-W, model B2HA does not come with a mounting template. The wall location for the frame, mounting bracket and all vents must be field calculated.
  • Page 21: Condensate Connection

    Condensate Connection/Neutralization Unit Vitodens 200-W B2HA 100 to 150 Technical Data Condensate Connection Condensate Drainage and Neutralization The condensate formed both in the condensing boiler and in the flue gas pipe must be discharged into the public sewage system in accordance with all applicable local regulations.
  • Page 22: Venting Options

    Venting Options/Electrical Connection/Control Vitodens 200-W B2HA 100 to 150 Technical Data Venting Options For detailed information refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System. Vent Connection, models B2HA 112, 150 Vent Connection, models B2HA 100 Electrical Connections...
  • Page 23: Boiler Control

    Boiler Control Vitodens 200-W B2HA 100 to 150 Technical Data On-Board Vitotronic 200, HO1B Control Modular structure Programming unit: Easy operation through: ■ The control unit is integrated into the boiler. The control – Plain text display with graphic ability unit comprises a standard unit, electronics modules and –...
  • Page 24: Design And Function

    Boiler Control Vitodens 200-W B2HA 100 to 150 Technical Data Design and Function Functions Setting the operating programs Weather-compensated control of the boiler water The heating system frost protection (see frost protection ■ and/or flow temperature function) applies to all heating programs.
  • Page 25 Boiler Control Vitodens 200-W B2HA 100 to 150 Technical Data Design and Function (continued) Technical Data Heating Curve Adjustment (slope and shift) The control unit regulates the boiler water temperature Rated supply voltage: 120 VAC (= supply temperature of heating circuit without mixing...
  • Page 26: Design And Functions

    Boiler Control Vitodens 200-W B2HA 100 to 150 Technical Data Design and Functions (continued) Room Temperature Sensor Boiler Temperature Sensor The boiler temperature sensor is connected at the control unit for weather-responsive operation and is built into the boiler. Max. ambient temp.
  • Page 27: Control Accessories

    Control Accessories Vitodens 200-W B2HA 100 to 150 Technical Data Vitotronic Control Accessories Immersion Temperature Sensor Mixing Valve Extension Module To capture the low loss temperature Specification Lead length fully wired: 12 ft. (3.75 m), Permissable ambient temp. - during operation: 32 to 194°...
  • Page 28 Control Accessories Vitodens 200-W B2HA 100 to 150 Technical Data Vitotronic Control Accessories (continued) KM BUS Expansion Module Vitotrol 200A (continued) To connect 2 to 9 devices (mixing valve actuator, Vitotrol, input module, etc.) to the single KM BUS connection of WS function: the boiler.
  • Page 29 Control Accessories Vitodens 200-W B2HA 100 to 150 Technical Data Vitotronic Control Accessories (continued) Vitotrol 300A (continued) Vitotrol 300A One Vitotrol 300A can be used for every heating circuit Connection: in a heating system. The Vitotrol 300A can regulate up - 2-core lead, length max.
  • Page 30 Accessories Vitodens 200-W B2HA 100 to 150 Technical Data Accessories for Vitodens 200-W Neutralization Unit for Single-Boiler Applications Low-Loss Header with neutralizing granulate for models B2HA 100, 112, 150 When used in conjunction with the Vitodens 200-W boiler, the low-loss header acts as hydraulic break, decoupling boiler and system circuits from each other.
  • Page 31 Accessories Vitodens 200-W B2HA 100 to 150 Technical Data Accessories for Vitodens 200-W Low-Loss Header (continued) IMPORTANT Low-loss header design (Type 80/50 or 120/80) Use only a Viessmann supplied temperature sensor. Do not use any other manufacturer’s temperature sensor. Legend...
  • Page 32: Standard Equipment

    Standard Equipment/Management System Vitodens 200-W B2HA 100 to 150 Technical Data Standard Equipment The Vitodens 200-W gas-fired condensing boiler with Wall mounting componentry Inox-Radial heat exchanger, modulating MatriX cylinder The following wall mounting components are supplied burner for liquid propane gas and natural gas (available...
  • Page 33: Hydraulic Connection

    Installation Vitodens 200-W B2HA 100 to 150 Technical Data Hydraulic Connection System design For apartments with less than 860 ft (80 m living Viessmann condensing boilers can generally be installed space or for low energy houses with low heat demand in any pumped hot water heating system (closed system).
  • Page 34: System Layout

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 1 Vitodens 200-W, B2HA with a direct-connected heating circuit Legend Installation of ... A Vitodens 200-W B2HA boiler with ■ radiator heating circuit (high-temp. circuit) Vitotronic 200, HO1B outdoor reset control DHW production ■...
  • Page 35: System Layout 2

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 2 Vitodens 200-W, B2HA with one heating circuit and low-loss header Installation of ... Legend Vitodens 200-W B2HA boiler with radiator heating circuit (high-temp. circuit) ■ Vitotronic 200, HO1B outdoor reset DHW production ■...
  • Page 36: System Layout 3

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 3 Vitodens 200-W, B2HA with... - DHW storage tank - one heating circuit with mixing valve and system separation Installation of ... Legend Vitodens 200-W B2HA boiler with underfloor heating circuit with 3-way mixing valve ■...
  • Page 37: System Layout 4

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 4 Vitodens 200-W, B2HA with... - DHW storage tank - one direct-connected heating circuit - one heating circuit with a mixing valve Installation of different heating circuits... Legend Vitodens 200-W B2HA boiler with radiator heating circuit (high-temp.
  • Page 38: System Layout 5

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 5 Vitodens 200-W, B2HA with... - DHW storage tank - one heating circuit with mixing valve - one heating circuit without mixing valve and low-loss header Legend Installation of different heating circuits...
  • Page 39: System Layout 6

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 6 Vitodens 200-W, B2HA with... - DHW storage tank - one heating circuit without a mixing valve - two heating circuits with a mixing valve - low-loss header Installation of different heating circuits...
  • Page 40: System Layout 7

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 7 Vitodens 200-W, B2HA with... - direct-connected heating circuit - one heating circuit with system separation Installation of different heating circuits... Legend radiator heating circuit (high-temp. circuit) ■...
  • Page 41: System Layout 8

    - low-loss header - multiple heating circuits with mixing valves - one heating circuit without mixing valve When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance. Legend Vitodens 200-W B2HA boiler with Vitotronic *1 Contact your local Sales Representative for details.
  • Page 42: System Layout 9

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data System Layout 9 Multiple (up to eight) Vitodens 200-W, models B2HA 100 to 150 with... - multiple heating circuits with mixing valves - low-loss header When designing a multiple Vitodens system as shown...
  • Page 43: Alternative Dhw Connection

    Installation Examples Vitodens 200-W B2HA 100 to 150 Technical Data Alternative DHW Connection The following piping diagram reflects an alternative connection for the DHW tank only and applies to system layouts 2, 5, 6 and 8. The boiler control pump logic function must be programmed in the Service Instructions.
  • Page 44: Wiring Diagram

    Wiring Diagram Vitodens 200-W B2HA 100 to 150 Technical Data Overview of Electrical Connections, Models B2HA 100 If any of the original wires as supplied with the appliance must be replaced. It must be replaced with the exact equivalent. WATER...
  • Page 45 Wiring Diagram Vitodens 200-W B2HA 100 to 150 Technical Data Overview of Electrical Connections, Models B2HA 100 (continued) Legend Outdoor Temperature Sensor Flow Temperature Sensor/Low Loss Header Boiler Temperature Sensor/High Limit Sensor Boiler Temperature Sensor/High Limit Sensor DHW Temperature Sensor...
  • Page 46 Wiring Diagram Vitodens 200-W B2HA 100 to 150 Technical Data Overview of Electrical Connections, Models B2HA 112 and 150 If any of the original wires as supplied with the appliance must be replaced. It must be replaced with the exact equivalent.
  • Page 47 Wiring Diagram Vitodens 200-W B2HA 100 to 150 Technical Data Overview of Electrical Connections, Models B2HA 112 and 150 (continued) Legend Outdoor Temperature Sensor Flow Temperature Sensor/Low Loss Header Boiler Temperature Sensor/High Limit Sensor Boiler Temperature Sensor/High Limit Sensor DHW Temperature Sensor...
  • Page 48: System Design Considerations

    System Design Vitodens 200-W B2HA 100 to 150 Technical Data System Design Considerations Low water cut-off IN THE COMMONWEALTH OF MASSACHUSETTS... this product shall be installed by a licensed plumber or A low water cut-off may be required by local codes.
  • Page 49 System Design Vitodens 200-W B2HA 100 to 150 Technical Data System Design Considerations (continued) System layout Oxygen diffusion barrier underfloor tubing The max. boiler water temperature for space heating The boiler warranty does not cover leaks resulting from ■ and DHW production is for model B2HA 100.
  • Page 50 Vitodens 200-W B2HA 100 to 150 Technical Data...
  • Page 51 Vitodens 200-W B2HA 100 to 150 Technical Data...
  • Page 52 Vitodens 200-W B2HA 100 to 150 Technical Data...

This manual is also suitable for:

Vitodens 200-w b2ha 112Vitodens 200-w b2ha 150

Table of Contents