Viessmann Vitodens 200-W B2HA 112 Installation Instructions Manual page 150

Wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 112:
Table of Contents

Advertisement

Troubleshooting
Fault Codes
(continued)
Fault code
Detailed fault
on display
code*2
F9
151
or
152
FA
154
FC
190
FD
227
-
FE
158, 159,
162 or 225
FF
224
N/A
2
5
6
8
29
33
*1 Control mode: Boiler/burner fully operational (fault code must be verified and reset).
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked: If fault cause is corrected, burner resumes operation.
*2 Detailed fault code coding address 38:xx (if available).
84
System behavior*1
Burner in fault mode
Burner in fault mode
Burner in fault mode
Burner in a fault state
and additional fault B7 is
displayed
Burner in a fault state
Burner in fault mode
Burner in fault mode
Burner in hold/wait state,
boiler not displaying fault
refer to coding address
38:XX
Vitodens 200-W B2HA 112, 150, 399, 530 Service
Cause
Fan speed too low
during burner start
Fan not at standstill
Gas valve faulty or faulty
modulation valve control;
or vent system blocked
Boiler coding card is
missing
Fault, burner control unit Check ignition electrodes and
Damaged or incorrect
boiler coding card or
main PCB
Internal fault or reset
button R blocked
Gas supply - no/low gas
pressure detected
Flame failure during
stabalization
Boiler temperature has
exceeded the monitoring
limit
Flue gas temperature has
exceeded the monitoring
limit
Open circuit at terminals
1 and L on Multi terminal
of the power pump
module.
Power supply voltage, is
below minimal operation
level, internal fuse
failure.
Corrective action
Check the fan, the fan cables
and power supply. Check the
fan control.
Press reset button R.
Check the fan, the fan
connecting cables and fan
control. Check the fan control.
Press reset button R.
Check the gas valve.
Check the vent system.
Press reset button R.
Insert the boiler coding card.
Press reset button R.
Replace control unit if fault
persists.
connecting cables. Check
whether a strong interference
(EMC) field exists near the
appliance. Press reset button R.
Replace control unit if fault
persists.
Press reset button R. If the fault
persists, check the boiler coding
card or replace it or the control
unit.
Restart the equipment.
Replace the control unit if the
equipment will not restart.
Check gas supply pressure
Check ionization electrode
Check boiler temperature sensor
Check flue gas temperature
sensor
Check connection at terminals 1
and L (jumper or installed safety
equipment of the Multi terminal
of the power pump module.
Check power, replace control