Viessmann Vitodens 200-W B2HA 112 Installation Instructions Manual page 122

Wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 112:
Table of Contents

Advertisement

Coding 2
General
(continued)
Coding in the factory setting
3C:0
3D:5
3E:0
3F:0
4B:0
56
Function input DE3 at extension
EA1: Not assigned
DHW recirculation pump
runtime for brief operation: 5
minutes
Internal circulation pump
stays in control mode at
signal "External blocking"
Internal circulation pump
stays in control mode at
signal "External demand"
Function input lH: Room
thermostat (Vitotrol 100) for
constant temperature control
Vitodens 200-W B2HA 112, 150, 399, 530 Service
Possible change
3C:1
Function input DE3: Heating
program - changeover.
3C:2
Function input DE3: External
demand with set flow
temperature.
Flow temperature setting:
Coding address 9B.
Internal circulation pump function:
Coding address 3F.
3C:3
Function input DE3: External
blocking.
Internal circulation pump function:
Coding address 3E.
3C:4
Function input DE3: External
blocking with fault message input
Internal circulation pump function:
Coding address 3E.
3C:5
Function input DE3: Fault
message input.
3C:6
Function input DE3: Brief
operation, DHW recirculation
pump (pushbutton function).
DHW recirculation pump runtime
adjustment: Coding address 3D.
3C:7
Input zone circuit 3, constant
3C:8
Input zone circuit 3, weather
compensated
3D:1
DHW recirculation pump off-delay
to
adjustable from 1 to 60 minutes.
3D:60
3E:1
Internal circulation pump stops
at signal "External blocking".
3E:2
Internal circulation pump starts
at signal "External blocking".
3F:1
Internal circulation pump stops
at signal "External demand".
3F:2
Internal circulation pump starts
at signal "External demand".
4B:1
External demand.
4B:2
External blocking.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents