Trip Amplifier 2/209
Software description
4.3

System parameters

System parameters help to analyse problems and locate faults.
EN
4.3.1
Software version P700 (read only)
This parameter gives access to the number of the current software version.
Example
2/209 V 1.18
4.3.2
Device ID P701 (read and write)
This parameter contains a device identification or TAG No. of up to 12 characters. It
does not have any influence on program execution. It can be employed to advantage
when storing data of several devices on a personal computer.
Example
2/209
4.3.3
Jumper KEY P704
Displays the status of the jumper KEY.
Example
Enter: P704 <Enter>
Display: P704 = 1 (1 = KEY ENABLE)
1 = push button changes unlocked
0 = push button changes locked
4.3.4
Jumper MODE P705
Displays the status of the jumper MODE.
Example
Enter: P705 <Enter>
Display: P705 = 0 (0 = MODE DISABLE)
0 = programming disabled
1 = programming enabled. Trips are NOT monitored
4.3.5
Jumper TEST P706
Displays the status of the TEST jumper.
Example
Enter: P706 <Enter>
Display: P706 = 0 (0 = TEST DISABLE)
1 = TEST Mode (calibration enabled)
0 = normal mode (calibration disabled)
30